9 refrigerant leak detection system (rlds), 1 diagnostic alarms, 10 copeland scroll — k5 refrigeration compressor – Emerson E2 User Manual

Page 71: 9 refrigerant leak detection system (rlds) -11, 1 diagnostic alarms -11, 10 copeland scroll – k5 refrig- eration compressor

Advertising
background image

ECT MODBUS

The RS485 Network and Hardware Setup

6

-

11

6.3.9

Refrigerant Leak Detection

System (RLDS)

The RLDS provides for the continuous monitoring of

refrigerant gas levels in up to 16 separate test zones or
channels. The instrument is programmed to monitor a
variety of gases and independent leak (small), spill
(medium), and evacuation (large) levels may be desig-
nated for each zone. The instrument also retains a log of
previous readings that can be accessed for analysis.

The RLDS has alarm level configuration parameters

that are synchronized. These will be read first from the
device. The E2 will be master of all other parameters. An
audible alarm and front panel indicators are provided to
signal alarm and fault conditions, and relay contacts are
provided that can be used to trigger external alarm devices
in the event of a system fault, or if a leak (small), spill
(medium), or evacuation (large) level of gas is detected.
The system also may be fitted with an optional two-chan-
nel 4-20mA current loop board for connection to remote
monitoring equipment.

The RLDS features full two-way communications via

an RS485 interface. MODBUS RTU is the communication
protocol standard and can be connected directly to an E2
controller version 3.02 and above. The RLDS is dynami-
cally licensed for 15 devices for RX/BX/CX 300-500 and
1 for RX100 and CX100 (same as IRLDS).

6.3.9.1

Diagnostic Alarms

6.3.10 Copeland Scroll – K5 Refrig-
eration Compressor

The Copeland Scroll — K5 Refrigeration Compressor

(Lrg Ref Scroll) application can monitor large type com-
pressors using the MODBUS network on E2 versions 3.02
and above. The Copeland Scroll — K5 Refrigeration is
supported on E2 CX-400, CX-100 and above. The E2
monitors and records compressor information, configura-
tion setup, status display, and alarm handling. The Cope-
land Scroll — K5 Refrigeration will be associated with the
suction group from the Compressor Association screen.
The scroll can be associated by pressing

 -

Controller Associations then

 - Compressor.

Figure 6-8

- RLDS

Diagnostic Alarm

Descriptions

Box Temp Fault

Chassis temperature is out of range

Bench Temp Fault

Sensor temperature is out of range

Manifold Pressure Fault

Pressure readings out of range

RS-485 Fault

Communication Error

Loop Fault

Current loop is open

Config. Fault

No zones are enabled

Zero Filter Fault

Charcoal filter needs repl.

Gain Set Fault

Gain setting is out of range

A2D Fault

A/D converter is not working

Zone Flow Fault

No flow during sample cycle

Purge Flow Fault

No flow during purge cycle

Over Range Fault

Conc. above measurable range

Zero Range Fault

Sensor voltage outside limits

Clipping Fault

Sensor output voltage too high

Table 6-7

-Diagnostic Alarm Outputs

Figure 6-9

- Compressor Association Screen