Ect modbus the rs485 network and hardware setup – Emerson E2 User Manual

Page 75

Advertising
background image

ECT MODBUS

The RS485 Network and Hardware Setup

6

-

15

CAUTION: If you change any dip switch
settings while the board is powered, disconnect
the power and re-power the board to reset.

WIRING FOR 640-0056, 56VA Transformer,

and 640-0080, 80VA Transformer

24VAC Center-Tapped Transformer

PRIMARY SIDE

240

208

C

120

(N

E

U

T

R

A

L

)

(H

O

T

)

120/208/240 VAC

L2

L1

Three-conductor non-shielded cables
are the recommended wire
for connecting between the
center-tapped transformer
and I/O boards.

Power Wiring Types:
14 AWG Belden 9495
18 AWG Belden 9493

SECONDARY SIDE

24V CT 24V

AC1

0V

AC2

AC1

AC2

0V

SHIELDED TWISTED PAIR
BELDEN #8761. FOR PLENUM,
USE BELDEN #82761 OR #88761
OR EQUIV.

WIRE + to + (same color)
WIRE 0V to 0V
WIRE - to - (same color)

BAUD RATE

1. Connect the 4AO board to the RS485 I/O Network.
2. Set the network address on the first five
rockers of dip switch S1.
3. Set the network baud rate using rockers 6
and 7 of dip switch S1.
4. Set RS485 termination jumpers UP (terminated) if at
either end of a daisy chain. Otherwise, set
jumpers DOWN (not terminated).
5. Optionally, connect the 4-20mA outputs in either a 2-wire
or 4-wire hookup as illustrated in Step 5, or if a 4-20mA is
not used, it may be left unconnected.
6. Connect board to the 24VAC

secondary

of the power transformer.

center-tapped

(Terminated)

(Not Terminated)

(Term)

(Term)

J9 J10 J11

J9 J10 J11

I/

O

N

E

T

Note:
Either the “2-wire” or “4-wire”
Hookup may be used at either
4-20mA output. The Hookups may
be the same or different. If a 4-20mA
is not used, it may be left unconnected.

“2-wire” 4-20mA
(Externally Powered)
Hookup example.
(Isolated)

+12V

+4-20

4-20 OUT
0V

+

+

_

_

24V

1-5V

Not Used

Not Used

4-20mA
Analog
Output

4-20mA
Analog
Output

“4-wire” 4-20mA
(Internally Powered)
Hookup example.
(Not Isolated)

+12V
+4-20

4-20 OUT
0V

_

+

250 ohms

Jumper

Grounded

1-5V

6

6

250 ohms

+

V

OUT

15-K

15-K

+

-

-

V

IN

NOTE: The voltage divide function capability
on the previous model (P/N 810-3030) 4AO board is
no longer supported. This can now be accomplished
by using two external 15-K resistors. If used with E2,
scale output range.

Advertising