Overview

Echelon Network and Hardware Setup

8

-

1

8

Echelon Network and Hardware Setup

8.1

Overview

Echelon is an optional, two-conductor network that interconnects E2s and other associated devices, such as CC-100

case controllers, TD3 temperature displays, and ESR8 evaporator stepper regulator boards. All Echelon devices are wired
together using the daisy-chain method of network structuring. If an Echelon network-enabled E2 is required, it must be
specifically ordered from Retail Solutions as an Echelon-enabled E2, and equipped with an Echelon plug-in card. See
Section 4.3.1, Echelon Card Plug-In (P/N 537-4860) with mounting screw (P/N 101-4201).

8.2

Wiring Type

Retail Solutions specifies one type of cable for Echelon Network wiring. This cable type’s properties are listed in

Table 8-1.

8.3

Echelon Network

Structuring (Daisy-Chains)

Echelon devices are networked together into configu-

rations called segments. A segment is a group of up to 64
Echelon devices that are connected together on an unbro-
ken series of wires.

The recommended way of constructing an Echelon

Network is called daisy-chaining. In the daisy-chain net-
work configuration, devices are arranged by subnets,
which consist of one E2 and all Echelon devices associ-
ated with the E2.

First, all devices in a subnet are connected in an unbro-

ken chain without branches or “star configurations” (see
Figure 8-1). Then, if more than one E2 is present on-site,
all chains are connected so that the entire network forms a

large unbroken chain, called a daisy chain
(see Figure 8-2). This allows for all devices in the Eche-
lon Network to be hard wired together for trouble free
communication.

Cable Type

Level 4, twisted pair, stranded, shielded

Wire Diam./AWG

0.65mm/22AWG

Loop Resistance

106(ohms/km)

Capacitance

49(nF/km)

Table 8-1

- Echelon Network Cable Specifications

Cable Type

Retail Solutions Part Number

1 pair, non-plenum

135-2300

1 pair, plenum

135-2301

Table 8-2

- Recommended Wiring