Lost Log Data-CRC Error

30

An internal error has occurred in E2, resulting in lost
log data.

Low Battery Voltage

99

The backup battery that keeps the time and date resi-
dent on the E2 main board may need to be replaced.

Low Limit Alarm

User

An HVAC application (AHU, Zone, RT-100, or
ARTC/MultiFlex RTU) has a temperature below one
of its heating setpoints.

Low Limit Notice

50

Network variable low limit exceeded.

Low Pack Superheat

11

Multiflex Pak ProAct superheat low limit exceeded.

Low Suction Limit Exceeded

User

The suction pressure has fallen below a Suction
Group’s low suction setpoint.

MIP Receive Buffer Overflow

20

Messages from the Echelon network are coming into
E2 too fast for the controller to process. This might
be caused by an E2 having too many applications
and/or logs running, or there may be too many Eche-
lon devices on the same segment as the E2 (i.e., more
than 63). If this message persists, call Retail Solu-
tions service.

Modem Didn't Initialize

20

E2 attempted to initialize the modem but failed.

Modem Init String Is Not Valid

30

The dial-out initialization string for the E2’s modem
is incorrect and may need editing.

Neuron Not Responding

20

The chip that handles Echelon networking on the E2
is either defective or in a mode that makes it non-
responsive. Contact Retail Solutions service for
assistance.

No Configuration Template

15

There is an internal error in the E2 software. Notify
Retail Solutions service.

No Description File

20

The Description File has failed to load onto the E2
when the Echelon device was commissioned. No
description file exists for the Open Echelon controller
being commissioned.

No Refrigerant flowing

Varies
depend-
ing on
applica-
tion type

Low or no refrigerant flowing.

No update has been received

Varies
depend-
ing on
applica-
tion type

No update has been received from the output point
connected to.

Normal Hi Limit Exceeded

User

An analog value has risen above its programmed Hi
Limit setpoint.

Alarm Name

Default

Priority

Definition

Advertising