The Comfort Alert diagnostic alarms are configurable

in the E2 as Disabled, Failure, Alarm, or Notice with an
accompanying priority setting. All Comfort Alert codes
will share the same advisory type and priority parameters.

High/Low Occ/Unocc Space Temperature Alarms

The thermostat does not provide alarming information

on either high or low temperatures for the Space tempera-
ture sensor. Therefore, the E2 application will provide this
functionality.

Supply Sensor Fail Alarm

The thermostat does not provide alarm information on

a failure of the supply temperature probe (if installed). The
E2 application will provide this functionality. Advisory
type, priority, and delay is provided for the supply sensor
fail advisory.

Conditions for Return to Normal (RTN) on Diag-

nostic Codes

The E2 application will issue an RTN on an active

advisory when the corresponding bit of the diagnostic
code goes to zero. If multiple diagnostic advisories are
active simultaneously, they will all return to normal when
the code reads zero.

Open Circuit

Compressor open circuit.

• Outdoor unit power disconnect is open.

• Compressor circuit breaker or fuse(s) is

open.

• Compressor contactor has failed open.

• High pressure switch is open and requires

manual reset.

• Open circuit in compressor supply wiring or

connections.

• Unusually long compressor protector reset

time due to extreme ambient temperature.

• Compressor windings are damaged.

Compressor open circuit

Open Start CircuitCompressor current only in run

circuit.

• Run capacitor has failed

• Open circuit in compressor start wiring or

connections.

• Compressor start winding is damaged.

Compressor open start circuit

Open Run Circuit Compressor current only in start

circuit.

• Open circuit in compressor run wiring or

connections.

• Compressor run winding is damaged.

Compressor open run circuit

Welded Contactor Compressor always runs.

• Compressor contactor has failed closed

• Thermostat demand signal is not connected

to module.

Welded Contactor

Low Voltage

Control circuit < 17VAC.

• Control circuit transformer is overloaded

• Low line voltage (contact utility if voltage at

disconnect is low)

Compressor Low Volt Trip

Protector Trip

Thermostat demand signal Y is
present, but the compressor is not
running.

• Compressor protector is open.

• Outdoor unit power disconnect is open.

• Compressor circuit breaker or fuse(s) is

open.

• Broken wire or connector is not making con-

tact.

• High pressure switch open if present in sys-

tem.

• Compressor contactor has failed open.

Protector Trip

Comfort Alert

Descriptions

Cause

E2 Advisory

Table 6-6

-Comfort Alert Outputs