Xev22d driver to e2 installation guide, Xev22d – Emerson E2 User Manual

Page 80

Advertising
background image

6-20

E2 RX/BX/CX I&O Manual

026-1610 Rev 13 14-SEP-2011

LAST XEV22D
DEVICE

13

14 15

17

1

2

4

5

+

_

16

XEV22D

13

14 15

17

1

2

4

5

+

_

16

MODBUS TERMINATION
BLOCK

150 OHM

TERMINATE LAST DEVICE ONLY

(P/N 535-2711)

MODBUS SHIELD TO
TERMINAL OF DEVICE

PIN 16

FROM E2 PIB BOARD OR
OTHER RS-485 MODBUS
DEVICE

WIRE BLACK TO +
WIRE WHITE TO

_

REVERSE POLARITY OF
+/- ON RS-485 CABLE
FROM E2 TO DEVICE

WIRE BLACK TO +
WIRE WHITE TO

1. Connect the MODBUS Network to the RS-485 Connector
on the E2 PIB board (Belden 8641 recommended).
2.

3. Position the three termination jumpers to the UP
(terminated) position to provide RS-485 termination at the E2.
4. Do not connect the shield of the MODBUS network to the
E2 PIB center terminal. Instead, use a 100 ohm ½ watt resistor
to connect the MODBUS cable shield to earth ground.
5. At the XEV22 device, wire the MODBUS cable to the RS-485 +/-
terminals and connect the MODBUS shield to the pin 16
terminal.
6. Terminate the end of the MODBUS network at the last device
on the daisy chain with the MODBUS termination block
(P/N 535-2711), or by connecting a 150 ohm resistor between
the MODBUS +/- terminals.
For more information, please refer to the XVE22D user manual

.

Note to wire the RS-485 +/- polarity at the E2 in the

reverse of the XEV22D device.

P/N 026-1206

XEV22D DRIVER TO E2

INSTALLATION GUIDE

0V

+

RS-485 -2A

0V

+

RS-485

637-4890 COM4 ON E2 PIB

HOT KEY

13

14 15

16 17

18

19

20

21

1

2

4

5

6

7

8

XEV22D

11

12

0V

+

RS-485 -2A

0V

+

RS-485

637-4890 COM4 ON E2 PIB

100 OHM
½ WATT

TO DEVICE

EARTH GROUND
CONNECTION

RESISTOR