2 hardware overview, 1 e2 hardware, 2 hardware overview -1 – Emerson E2 User Manual

Page 25: 1 e2 h, Ardware, 2hardware overview

Advertising
background image

E2 Hardware

Hardware Overview

2

-

1

2

Hardware Overview

This section gives an overview of the E2, the hard-

ware, and how it communicates across the I/O and Eche-
lon Networks to control an entire system.

2.1

E2 Hardware

The E2 controller is programmed to monitor and com-

mand all aspects of a refrigeration or building environ-
mental control system. The E2 uses both an RS485 I/O
Network and a LonWorks Network to gather data from
input devices, communicate with other E2s, and activate
or deactivate loads.

In general, an E2 control network will consist of the

following components:

1.

E2 - The “brain” of the control network, which
performs all necessary computations and sends
commands to the output devices that control the
system.

2.

Input Boards - Transfer readings to the E2.

3.

Output Boards - Banks of relays, digital pulse
outputs, or analog outputs, which the E2 may use
to control loads.

4.

Smart Boards - Boards such as case controllers
(for refrigeration) or rooftop controllers (for
building control) that perform control functions
for an individual case or rooftop unit, and send
the data to the E2 for logging and alarm purposes.

5.

Modem - For remote communication via phone,
if necessary.

6.

Network Wiring - Wiring that connects the E2 to
other E2s, and all the input, output, and smart
boards.

7.

Sensors and Loads - The “eyes” and “hands” of
the control network. Sensors “see” what needs to
be controlled on the network, and Loads are what
can be controlled, or more specifically, be turned
on and off, such as compressors, condensers,
lights, and fans.

Figure 2-1

- E2 Front Panel

Dimensions

Standard Mount:

9.06” W x 12.06” H x 3.75” D

Recessed Mount:

9.06” W x 10.56” H x 2.0” D

Base:

10.56” W x 10.56” H x 3.75” D

Operating

Temp

-40°F to 149°F (-40°C to 65°C)

Storage Temp

-40°F to 158°F (-40°C to 70°C)

Operating

Humidity

5% - 95% RH non-condensing at 90°F

Storage

Humidity

5% - 100% RH

Power

24 VAC ±20%, 50/60 Hz, Class 2

VA Load

50

Table 2-1

- E2 Specifications

NOTE: Contact Retail Solutions Customer
Service at 770-425-2724 for E2 controller
part numbers and model descriptions.

Advertising