3 ect modbus, 1 control techniques drive (vsd), 2 copeland discus with coresense diagnostics (isd) – Emerson E2 User Manual

Page 66: 3 xr35cx, xr75cx, and xev22 case controllers, 1 xr75cx-case display, 3 ect modbus -6

Advertising
background image

6-6

E2 RX/BX/CX I&O Manual

026-1610 Rev 13 14-SEP-2011

above may communicate with IMC/Prodigy rooftop units
equipped with IMC/Prodigy control boards version M4-1
or higher. E2 controllers version 2.30F01 and above may
use any of the RS485 I/O ports (COM2, COM4, or
COM6) as a IMC/Prodigy communication port. Version
2.21F01 E2 units may only connect IMC/Prodigys to an
RS485 Expansion Card. Connectivity to IMC/Prodigy is a
licensed feature and must be purchased from Retail Solu-
tions.

The IMC/Prodigy interface has its own technical bulle-

tin explaining installation, network setup, and E2 configu-
ration. Refer to Technical Bulletin 026-4117.

6.3

ECT MODBUS

E2 controllers version 2.30F01 or greater may select

ECT MODBUS as a network type. The E2 communicates
with MODBUS devices including but not limited to Con-
trol Link CD, Control Link RSC, and Control Link ACC.

The Control Link products have their own documents

explaining device configuration, networking, and E2
setup:

026-4600 - Control Link RSC Installation Instruc-

tions

026-4601 - Control Link CD Installation Instruc-

tions

026-4703 - Control Link ACC Installation Instruc-

tions

026-4602 - Control Link ECT MODBUS Network-

ing to E2s (covers MODBUS installation for all
Control Link models)

6.3.1

Control Techniques Drive

(VSD)

Using the MODBUS network type, E2 controllers can

communicate with the Control Techniques variable-speed
drive (VSD). There are three different VSD models the E2
communicates with: Commander SE, Commander SK,
and Unidrive SP drive types.

Note that all CT drives are 2 stop bits, with no parity.

Since ECT MODBUS specifies 1 stop bit, CT drives will
configure the General Services setting for stop bits and
always communicate with the drives using 2 stop bits. The
E2 calculates the difference and adjusts for the additional
stop bit.

Configure the COM port the CT drive will connect to

by pressing Alt + M to open the serial configuration man-
ager. Set the COM port to MODBUS and the baud rate
(match the baud rate on the CT drive). For more informa-
tion on setting up serial ports, go to Section 5, Serial Con-

figuration.

The Control Techniques VSD has its own technical

bulletin that explains interfacing with E2 (P/N 026-4122).
The installation and operation manual explaining the VSD
is maintained by Control Techniques. Contact your Con-
trol Techniques representative for a copy of this manual.

6.3.2

Copeland Discus with Core-

Sense Diagnostics (ISD)

E2 controllers version 2.21F01 and above may com-

municate with Copeland ISD compressors using the ECT
MODBUS network. E2 controllers version 2.30F01 and
above may use any of the RS485 I/O ports (COM2,
COM4, or COM6) as a Copeland ISD communication
port. Version 2.21F01 E2 units may only connect Cope-
land ISD compressors to an RS485 Expansion Card.

The installation and operation manual explaining the

Copeland ISD interface is maintained by Copeland. Con-
tact your Copeland representative for a copy of this man-
ual.

6.3.3

XR35CX, XR75CX, and

XEV22 Case Controllers

E2 controllers version 2.84 or greater communicate

with the XR and XEV controllers. The XR and XEV con-
trol compressor regulation, defrost, light, and evaporator
fans in refrigeration systems on normal, low, or medium
temperatures, control a wide variety of stepper electronic
expansion valves and anti-sweat heaters (if present), and
measure and regulate the superheat of the refrigerant in the
system.

If the case controller is configured with a Real Time

Clock (RTC), it can be programmed with up to 6 daily
defrosts and an energy saving function. Without the RTC,
the E2 can coordinate defrost cycles and the energy-saving
function.

Several parameters of the Emerson controllers (such as

inputs, outputs, setpoints, and alarms) can be configured
directly in E2 and sent to the appropriate Emerson control-
ler, depending on the controller model.

6.3.3.1

XR75CX-Case Display

E2 controllers version 3.02 or greater communicate

with the XR75CX-Case Display controller. The XR75CX-
Case Display is a microprocessor-based controller, suit-
able for applications on medium or low temperature venti-
lated refrigeration units. It has up to four (4) analog inputs:
discharge air temperature, product temperature, defrost
temperature and coil out temperature, four (4) relay out-
puts, and up to two (2) digital inputs. For more informa-
tion on the XR75CX-Case Display, refer to the XR75CX-

Advertising