2 power connection, 2 power connection -2 – Emerson E2 User Manual

Page 96

Advertising
background image

9-2

E2 RX/BX/CX I&O Manual

026-1610 Rev 13 14-SEP-2011

9.1.2

Power Connection

If power is needed to operate the sensor, several termi-

nals exist on the 16AI, Multiflex boards, 8IO, that may be
used to supply DC power (see Figure 9-3 for 16AI and
MultiFlex power connections).

Input boards may supply 12VDC or 5VDC. To connect

to one of the DC power sources, simply connect the sen-
sor’s power wire to one of the terminals.

The maximum current that may be drawn from the

+12VDC terminal is 100 milliamps. The maximum cur-
rent that can be drawn from all three +5VDC terminals
COMBINED is 50 milliamps.

Specific wiring instructions for each type of sensor are

given in Table 9-1 on page 9-3.

Figure 9-2

- Input Type Dip Switches for MultiFlex 16 and 16AI

Boards

26501070

2

2

3

3

4

4

5

5

6

6

7

7

8

8

1

1

ON

ON

S2

S1

INPUTS 9-16

INPUTS 1-8

Set DOWN for
sensors requiring
voltage

Set UP for
sensors not requiring
voltage

Figure 9-3

- Input Board Power Sources

NOTE: For 24VAC sensors, a separate trans-
former must be used unless specified other-
wise in Table 9-1 on page 9-3.

Advertising