The I/O Network

The RS485 Network and Hardware Setup

6

-

3

• Avoid running cable next to noise-generating

devices, such as motor starters, contactors, invert-
ers, fluorescent light ballasts, arc welders, etc. If
possible, keep cable less than 1 foot away from
noise-generating devices (ideally, at least 5 feet).

• Do not run RS485 cable in the same conduit as

high-voltage wiring, such as 120VAC or 240VAC
power wiring. Keep RS485 cable a minimum of 3
inches away from high-voltage wiring (ideally, at
least 12 inches). If RS485 must cross paths with
high-voltage wiring, cross them perpendicular —
running RS485 and high-voltage wire in parallel
increases the amount of noise induced on the net-
work.

• Ensure you are grounding each input device’s 0V

power terminal to a separate earth ground, and set-
ting the termination and biasing jumpers as
instructed in Section 6.1.8, Setting the Terminating
and Biasing Jumpers
.

For more instructions on best practices for minimizing

noise, refer to publication 026-1903, E2 Controller Wir-
ing Practices
, available in the Product Manuals section of
the Emerson Climate Technologies Web site:
www.emersonclimate.com

6.1.6

Network ID Numbers (Board

Numbers)

Each device on an RS485 segment has either a network

dip switch or rotary dials that must be used to assign the
board a unique network ID number.

The network ID number makes a board unique from

other boards on the network of the same type. This allows
E2 to find it and communicate with it easily.

Boards of the same type should be numbered in

sequence, starting with one and continuing with two,
three, and so forth. For example, if a segment contains
four 16AI boards and five 8RO boards, you should num-
ber the 16AIs one, two, three, and four; and the 8ROs one,
two, three, four, and five. The same should be done with
multiple 4AO and 8DO boards, and IRLDS leak detection
units.

For all boards, except 8IO and 8DO boards, the net-

work dip switch labeled S1 (or S3 for the 16AI board) is
used to set the unique board number of the unit and the
baud rate. The 8IO and 8DO uses rotary dials to set the
board number of the unit.
Numbering the MultiFlex Combination I/O Boards

When it comes to network numbering, the MultiFlex

Combination Input/Output boards (88, 88AO, 168,
168AO, and 168DO) are special cases. They are actually a

combination of three types of Retail Solutions boards: the
inputs are configured like a 16AI, the relay outputs are
configured like an 8RO, and the analog outputs are config-
ured like a 4AO.

When a MultiFlex combo board is present on the net-

work, it must be addressed like all three board types.
Therefore, when numbering these boards, you must set a
unique number for both the 16AI, 8RO, and 4AO compo-
nents of the board.
Addressing the MultiFlex Boards

For MultiFlex boards, set positions 1 to 5 on S3 for the

16AI component and positions 1 to 5 on S4 for the 8RO
component. Set positions 6 to 8 on S4 for the 4AO or 4DO
segment. For MultiFlex board controllers, use positions 1
to 5 on S3 to set the address.
Addressing the MultiFlex ESR Boards

The MultiFlex ESR uses standard Retail Solutions I/O

Network addressing. Set positions 1 to 5 on S1 to set the
network ID (address) of the MultiFlex ESR from 1 to 31.

6.1.7

Setting the Baud Rate

All I/O boards have dip switches that determine the

baud rate at which they communicate. Currently, the baud
rate dip switch in network components may be set at either
4800, 9600, 19200, and 38400. Setting of the baud rate is
accomplished using dip switches (refer to the board’s
installation sheets at the end of this section for specific dip
switch settings).
Baud Rate for the E2

The baud rate default for E2 is 9600.

Baud Rate for the Gateway

The Gateway can be set to either 9600 baud or 19.2K

baud by dip switch #6. “ON” places the rate at 9600 baud
while “OFF” sets it at 19.2K baud.

Dip switches 6 and 7 control the baud rate at which

the Gateway communicates with the site controller on the
RS485RS485 Network. These switches must be set to the
same baud rate setting as the E2 or REFLECS (usually
9600 baud).

Dip switch 8 controls the baud rate at which the Gate-

way communicates with the other devices on the Receiver
Bus Network. This baud rate may only be set to either
9600 baud (switch DOWN) or 19200 baud (switch UP).
All Gateways and receivers on the Receiver Bus Network
must have the same baud rate dip switch setting. It is rec-
ommended you use 9600 baud as the Receiver Bus Net-
work baud rate.

Baud Rate for the 8IO, 8DO, and ARTC

There are three I/O devices that do not have baud rates

determined by dip switches. They are as follows: