Emerson E2 User Manual

Page 236

Advertising
background image

C-14

E2 RX/BX/CX I&O Manual

026-1610 Rev 13 14-SEP-2011

User Cleared All Applications

50

A user has cleared out all data from all applications in
this E2.

User/Appl. Forced Reset

50

A user or an application has forced a reset of this E2.

VS Alarm

20

Multiflex PAK variable speed device alarm.

VS Inverter Fail

User

A variable-speed inverter driving a variable-speed
fan or compressor has failed.

WCC Controller Alarm

20

Woodley case controller alarm.

WPK Controller Alarm

20

Woodley Pack Amps Fail alarm.

Watchdog Countdown Hit Zero

20

E2 locked up while trying to perform a task. If this
alarm occurs often, there may be a problem with your
system. Contact Retail Solutions service.

Watchdog Reset Timer Failed

20

E2 tried to reset itself to clear a hung task, but the
“watchdog” feature on the E2 was disabled. Check
the jumper J19 labeled “Watch Dog” on the E2 main
board. This jumper should be either be set to
“ENABLE” or it should not be present at all.

X300<->X300 Links Lost-CRC Err 20

An internal error has caused a loss of communication
between E2s.