7 zone control, 1 overview, Ontrol – Emerson E2 User Manual

Page 167: 1 overview -25, Section 11.7, zone control

Advertising
background image

Zone Control

Software Overview

11

-

25

11.7 Zone Control

11.7.1 Overview

An HVAC Zone is a collection of up to sixteen rooftop

units or air handling units that work together to maintain
the same temperature and humidity throughout a particular

volume of space. The primary function of an HVAC Zone
is to “manage” the operation of each individual HVAC
unit by providing the temperature setpoints that will be
used in Temperature Control. Zones are also responsible
for ordering HVAC units to dehumidify and determining
when outside air conditions are favorable to economize.

Outdoor Air Humid

Humidity

Set up as Out-
door Humidity
Provider in
Global Data (see

Section 10.17

).

Curtailment Device

Digital

Set up as Curtail-
ment in Global
Data (see

Sec-

tion 10.17

).

Fan Proof

Digital

See Table 9-1 on
page 9-3

Fan Proof Reset

Digital

See Table 9-1 on
page 9-3

VS Inverter Alarm

Digital

See Table 9-1 on
page 9-3

Enthalpy Switch
(Indoor and/or Out-
door)

Digital

See Table 9-1 on
page 9-3

Dewpoint Probe (for
Economization)

Dewpoint

See Table 9-1 on
page 9-3

Mixed Air Temp (ana-
log economizers only)

Temperature

See Table 9-1 on
page 9-3

Inputs

Sensor Type

Wiring

Instructions

Table 11-10

- Suction Group Inputs

Output Device

Wire 8RO

contacts to:

Set Fail-safe Dip

Switch to:

Notes

Heat / Cool Staged
Outputs

see note

see note

Set up any stages you want ON when the controller is off-line as
N.C. Stages you want OFF should be set as N.O.

Single-Speed Fans

see note

see note

If one or more heat or cool stages will be ON, wire fan N.C. so
it will be active during controller off-line times. Otherwise, wire
N.O.

Two-Speed Fans
(LOW, HIGH, and
fan contactor)

see note

see note

If any heat or cool stages are configured to be ON (N.C.), set the
wiring and the switch to N.C., and set either the LOW or HIGH
stage output to N.C. (whichever speed you want active). If no
heat or cool will be active, set LOW, HIGH, and the fan contac-
tor to N.O.

Digital Economizer

N.O.

N.O.

Table 11-11

- Suction Group Outputs