Emerson E2 User Manual

Page 233

Advertising
background image

Appendix C: Alarm Advisory Messages

C

-

11

Normal Low Limit Exceeded

User

An analog value has fallen below its programmed Lo
Limit setpoint.

Not Enough Backed Memory

10

The E2 tried to save data to the battery-backed mem-
ory, but the memory was full.

Not Enough Flash Memory

20

The E2 tried to save data to the flash memory, but the
memory was full.

Not Enough Memory

10

The E2 tried to save data to unbacked memory, but
the memory was full.

Not Enough Scatch Pad Memory

50

The E2 tried to save data to the scratch pad memory,
but the memory was full.

Notice Limit Exceeded

User

An analog sensor’s programmed notice limit has
been exceeded.

Num. Of Events Exceeded Limit

User

A digital value has transitioned ON more times than
its defined Number of Events setpoint.

Occupied Hi Limit Exceeded

User

An analog value has risen above its defined high limit
setpoint during OCCUPIED mode.

Occupied Low Limit Exceeded

User

An analog value has fallen below its defined low
limit setpoint during the OCCUPIED mode.

Off Time Exceeded Limit

User

A digital value has been OFF longer than its defined
Time Off Last setpoint.

Oil Failure Occurred

User

An oil sensor for a compressor has detected a failure.

On Time Exceeded Limit

User

A digital value has been ON longer than its defined
Time On Last setpoint.

Open Wire

30

MultiFlex ESR controller has detected an open wire
on the valve input.

Overcurrent

30

MultiFlex ESR controller has detected an overcurrent
condition on the valve.

Override Log lost - CRC Error

20

An internal error in the E2 has resulted in a loss of the
override log.

Override Lost Output Cleared

20

A user tried to override an output on a CC-100, RT-
100, or similar Echelon device, but the override was
not performed successfully. Try the override com-
mand again. If this alarm persists, call Retail Solu-
tions service.

Override Operation Didn't Take

20

The E2 tried to carry out an override and was unsuc-
cessful.

Override State Not Restored

50

An overridden input or output has remained in the
override state longer than its programmed time.

Pad Memory Corrupted - Reboot

30

A problem with memory has resulted in a reset of the
E2.

Part Cnfg Loss-Ptr

15

Due to an internal error, part of E2’s configuration
data has been lost.

Alarm Name

Default

Priority

Definition

Advertising