7 leds, 8 open echelon device connectivity, 1 configuring echelon devices – Emerson E2 User Manual

Page 90: 7 led, Chelon, Evice, Onnectivity, 1 configuring echelon devices -4

Advertising
background image

8-4

E2 RX/BX/CX I&O Manual

026-1610 Rev 13 14-SEP-2011

2.

Use a transformer that has a power rating
equal to or higher than the total calculated
VA (see Table 8-3).

Example: Boards totaling 48VA can be connected to

either a 50VA or 75VA transformer.

Refer to the installation guides on the next few pages

for instructions on how to install these boards on the Eche-
lon Network.

8.7

LEDs

The Echelon Board LEDs can be used to determine the

status of normal operating parameters for the board.

8.8

Open Echelon Device

Connectivity

Open-Echelon E2s must be ordered pre-configured

from Retail Solutions. Open-Echelon licenses must be
purchased and enabled on units, and are not transferrable
to other units without assistance from Retail Solutions.
Call 770-425-2724 for technical assistance or your sales
representative. Your sales representative will know which
devices your unit will connect to.

8.8.1

Configuring Echelon Devices

Login to the controller and enter the desired number of

Echelon devices to be added in the Connected I/O screen.
From the Main Menu:

1.

Select

(System Configuration)

2.

Select

(Network Setup)

Unit

amps

VA

VAC

Center

tapped?

E2

1.66

40

24

No

ESR8

2.4

75

24

No

TD3

0.11

4

24

No

CC-100/

CS-100

Power supplied by Power Module

Table 8-4

- Device Power Requirements

2

4VA

1

40VA

+

48VA

=

Echelon Board

Status

Red (D1) (Reset)

ON: The Echelon port is being
held in reset or if momentary it
means the board has gone
through reset

Red (Service)

During normal operation this
LED should be off. If the Ser-
vice Pin is pressed, this LED
will come on.

If the LED is blinking, the node
does not have its Subnet/
Node address set. (E2 should
set this during the first power -
up sequence where the user
will be asked in which Subnet
to put the controller (E2 will al-
ways be Node = 1 on the net-
work).

If the LED is blinking, then try
resetting the E2. If this does
not correct the problem, re-
place the Echelon board.

ON (no blinking): Replace the
Echelon board. The Neuron
processor has lost its applica-
tion program.

Table 8-5

- Echelon LED Status