12.11.1.2 Setup Screens

When setting up an application using a Setup screen

(see Section 10.7.2, Status Screens) all inputs and outputs
that are set up to be logged will be marked with an L on
the right-hand side. From the Setup screen, you may
access the logs of these inputs by pressing

.

12.11.1.3 Setting Up Input and Output

Pointers

Pointers allow a property to get or send its value to

another property, and are a way to transfer information or
values (input and outputs) from one application to another
within a controller.

For example, if you are setting up a Suction Pressure

pointer, you are specifying the location of where the Suc-

tion Pressure is coming from. Note that:

• An output pointer can be connected to multiple

input pointers

• A single input pointer cannot be connected to mul-

tiple output pointers

• Pointers can be set up for all applications

To set up pointers from a Setup screen:

1.

Press

 (SETUP) from the desired applica-

tion’s Status screen. (If starting from the Home
screen, move the cursor to the desired applica-

tion’s value and press

to open the Actions

Menu. Choose Setup. This will take you to the
Setup screen.)

2.

Once inside the application’s Setup screen, use
the

 and  keys to highlight the Inputs

and Outputs index tabs.

3.

Press

 (EDIT) to open the Edit menu.

4.

Choose Alternate I/O Formats to open the for-
mat menu.

5.

Choose one of the pointer formats.

If you are in the Inputs setup and have selected Area

Ctrl: Application: Property as the pointer format, the
third column (the Output field) is the output that you are
pointing (connecting) the input to. If you are in the Out-
puts
setup and have selected Area Ctrl: Application:
Property
as the pointer format, the third column (the
Input field) is the input that you are pointing (connecting)
the output to.

Changing the format to a Fixed Value will give you

the option of entering a value in the field that will be read
by the input instead of being hooked to a board:point or
another cell.

For information on naming conventions for E2 control-

lers, applications, and points, see Section 12.13, Naming
Conventions for E2 Controllers, Applications, and Points
.