9-16

E2 RX/BX/CX I&O Manual

026-1610 Rev 13 14-SEP-2011

the appropriate cable type.

P/N 335-3263 (Pulse Valve)

Figure 9-16 shows the connections for pulse valve 1

and pulse valve 2. The pulse valve 2 leads (BLACK/
GREEN) may be clipped if a second evaporator is not
present on the case.

P/N 335-3261 (Sporlan SEI and Emerson Flow Con-
trols ESR Stepper Valve)

The 335-3261 valve cable is equipped with a four-pin

male connector that plugs into a four-pin female connector
on the valve. Plug the valve cable connector into the valve
connector.

P/N 335-3260 (Generic Stepper and Emerson Flow
Controls ESV Valve)

The 335-3260 valve cable has six flying leads for con-

nection to a stepper valve. Four of these leads connect to
the stepper motors, while the other two serve as the power
wiring (+12VDC and ground).

The pinout for this valve cable is shown in Figure 9-

17. Table 9-5 shows how to hook the flying leads to Emer-
son Flow Controls ESR, Emerson Flow Controls ESV, and
Sporlan SEI & CDS valves.

9.4

ESR8 Valve Output

Wiring

The stepper valves are wired to the board by connect-

ing the four-conductor wire from the stepper valve to a
connector plug and then plugging in to one of eight jacks
along the top of the board

Figure 9-18

.

Use the cable har-

nesses supplied with the valves or use Belden #9418 four-
conductor 18AWG wire.

If the stepper valves have block-style connectors, cut

the ends off and attach the terminal plugs supplied with the
ESR8 to the wire ends.

Figure 9-16

- Wiring the 335-3263 Valve Cable

Figure 9-17

- Wiring the 335-3260 Generic Stepper Valve

Wire on Valve

Cable 335-3260

Emerson

Flow Con-

trols ESR

Emerson

Flow Con-

trols ESV

Sporlan

SEI&CDS

Pin #

Color

1

Red

Red

Blue

Red

2

Black

Blue

Red

Green

3

Blue

Black

Black

Black

4

Green

White

White

White

5

White

Yellow

6

Brown

Table 9-5

- 335-3260 to Valve Connection Information

NOTE: A wire run may not be longer than 150
ft. using Belden #9418.