Emerson E2 User Manual

Page 99

Advertising
background image

The 16AI, 8IO, and MultiFlex Inputs

Input and Output Setup

9

-

5

207-1000 Refrigerant

Level Trans-
ducer (Hansen
Probe)

Down

1.

Wire BLACK ground
wire from “GND”
sensor terminal to odd
numbered board ter-
minal.

2.

Wire GREEN signal
wire from “SIGNAL”
sensor terminal to
even numbered board
terminal.

3.

Wire RED power wire
from “POWER” sen-
sor terminal to
+12VDC terminal on
board.

203-1902 Dewpoint

Probe

Up

1.

Connect the WHITE
and GREEN wires to
AC1 and AC2 power
terminals.

2.

Connect BLACK
ground wire to odd
numbered board termi-
nal.

3.

Connect RED signal
wire to even numbered
board terminal.

P/N

Sensor

Input Type

Dip Switch

Wiring

Table 9-1

- Sensor Wiring