ECT MODBUS

The RS485 Network and Hardware Setup

6

-

21

1. Connect the MODBUS Network to the RS-485 Connector on the
E2 PIB board (Belden 8641 recommended).
2.

3. Position the three termination jumpers to the UP (terminated)
position to provide RS-485 termination at the E2.
4. Do not connect the shield of the MODBUS network to the E2 PIB
center terminal. Instead, use a 100 ohm ½ watt resistor to connect
the MODBUS cable shield to earth ground.
5. At each device, wire the MODBUS cable to the RS-485 +/- terminals
and connect the MODBUS shield to the pin termi

nal.

6. Terminate the end of the MODBUS network at the last device on
the daisy chain with the MODBUS termination block (P/N 535-2711),
or by connecting a 150 ohm resistor between the MODBUS
+/- terminals.
For more information, please refer to the XR35CX user manual
-

and the XR75CX user manual -

P/N 026-1203

P/N 026-1210.

Note to wire the RS-485 +/- polarity at the E2 in the reverse of

the XR35CX or XR75CX device.

18

NOT TERMINATED

TERMINATED

RS-485 I/O or MODBUS Net

HOT KEY

16

17 18

19 20

21

22

23

24

1

2

3

4

5

6

7

8

XR35CX, XR75CX TO E2

INSTALLATION GUIDE

0V

+

RS-485 -2A

0V

+

RS-485

637-4890 COM4 ON E2 PIB

BELDEN 8641

100 OHM
½ WATT

TO DEVICE

EARTH GROUND
CONNECTION

RESISTOR

MODBUS TERMINATION
BLOCK (P/N 535-2711)

150 OHM

TERMINATE LAST DEVICE ONLY

TERMINAL XR35CX/XR75CX

MODBUS TERMINAL
BLOCK

FROM OTHER RS-485
MODBUS DEVICE

0V

+

RS-485 -2A

0V

+

RS-485

637-4890 COM4 ON E2 PIB

OBSERVE WIRE
COLOR POLARITY

SHIELDED TWISTED
PAIR
RECOMMENDED

BELDEN 8641

REVERSE POLARITY OF
+/- ON RS-485 CABLE
FROM E2 TO DEVICE

100 OHM
½ WATT

WIRE BLACK TO +
WIRE WHITE TO

_

WIRE WHITE TO +
WIRE BLACK TO

_

XR35CX/XR75CX

XR35CX / XR75CX

DEVICE

COM 4