3 defrost termination, Pulsed defrost, 4 emergency defrost – Emerson E2 User Manual

Page 149: 5 hot gas defrost with esr8 and multiflex esr, 3 clean and door switches, 1 clean switches, 2 door switches, 3 clean and door switches -7, 1 clean switches -7 11.3.3.2 door switches -7

Advertising
background image

Standard Circuits

Software Overview

11

-

7

will turn the Defrost output ON to activate the heaters con-
nected to the output.

Any user-defined Pump Down and Run-Off times will

be observed as normal.

11.3.2.3 Defrost Termination

Both the start and the end times of a defrost cycle are

determined by the user. The Pump Down, Defrost, and
Run-Off stages all have fixed durations, and when the last
stage of the cycle is complete, defrost is terminated.

However, a Standard Circuit application may be pro-

grammed to terminate the Defrost stage of the defrost
cycle early if the temperature inside the case rises above a
fail-safe temperature setpoint (called the termination set-
point). For certain defrost types, defrost heat may also be
“pulsed” in order to keep the temperature below the set-
point without terminating defrost.
Pulsed Defrost

Pulsed Defrost is only available if the circuit is using

heated defrost, such as Electric or Hot Gas defrost.

Pulsed Defrost is similar to the Temperature Termina-

tion strategy outlined in Section 11.3.2.3, except a defrost
cycle always continues for the full programmed duration.

When the termination temperature rises above the set-

point, defrost does not end. Instead, the defrost heat is
turned OFF until the case temperature falls below the set-
point, at which time the output will come back ON to con-
tinue heating.

Figure 11-4 illustrates what happens in a pulsed

defrost cycle. In this example, the case reaches its termina-
tion temperature approximately 2/3 of the way into its
defrost cycle. Defrost continues, but defrost heat is turned

OFF until the temperature falls below the setpoint, at
which point the heat is turned back ON.

Defrost heat will continue to be pulsed in this manner

until the defrost time has passed. The defrost cycle will
then begin the Run-Off period, and then restart refrigera-
tion.

11.3.2.4 Emergency Defrost

When necessary, a user can initiate an emergency

defrost cycle in a circuit. Emergency defrost cycles are
similar to normal defrost cycles, except an emergency
defrost cycle will ignore all calls for termination and
remain in defrost for the entire programmed defrost time.
For cases using a pulsed defrost strategy, this means the
defrost heat will not be pulsed during emergency defrost.

Emergency defrosts are initiated by the user from the

Standard Circuit Bypass screen (see Section 12.6, Manual
Defrost and Clean Mode
).

11.3.2.5 Hot Gas Defrost with ESR8 and

MultiFlex ESR

If an ESR8 or MultiFlex ESR is used on a circuit that

uses hot gas defrost, values for circuits in defrost are
forced OPEN (100%) to allow hot gas to flow through the
evaporators.

11.3.3 Clean and Door Switches

11.3.3.1 Clean Switches

A Standard Circuit application may be configured to

entirely shut down a case circuit so that it may be cleaned
or serviced. A case circuit enters clean mode when it
receives a signal from an input called the clean switch.

Clean switches may be set up as either “Switched” or

“Timed.” If a clean switch is configured as “switched,” the
circuit enters clean mode when the switch is turned ON,
and it remains in clean mode until the switch is turned
OFF. If a clean switch is configured as “timed,” the circuit
enters clean mode when the switch is turned ON, and it
remains in clean mode for a fixed user-defined amount of
time.

During clean mode, the Fan, Defrost, and Refrigera-

tion Solenoid outputs are all turned OFF, and the liquid
line solenoid is CLOSED.

If desired, a notice may be sent to the E2’s Alarm Log

so that the E2 can keep track of clean modes and times.

11.3.3.2 Door Switches

Walk-In Box freezers are often equipped with door

switches that disable the evaporators when the door is
open. The E2 is capable of reading a digital door switch
input and controlling the freezer appropriately.

When a door switch opens, the E2 will shut off the

Figure 11-4

- Defrost Termination (Pulsed)

Advertising