Omron Programmable Terminals NT631C User Manual

Page 102

Advertising
background image

85

Connecting to the Host’s RS-232C Port

Section 5-1

Usable Cables with Attached Connectors:

• For host link, 1:1 NT Link, or 1:N NT Link (+5 V power supplied from PLC)

XW2Z-070T-1(9-pin to 9-pin, 0.7 m)
XW2Z-200T-1(9-pin to 9-pin, 2 m)

CVM1/CV-series CPU Units whose model names do not have the suffix -EV

@

cannot be connected by any connection method.

When connecting to the peripheral port of a CS/CJ-series CPU Unit, a CS1W-
CN118 Connecting Cable is required in addition to the above cables. (Supply
power to the +5-V output of the NT-AL001 from an external power supply
when using this method.)

• When using the host link or NT Link (1:1) method, short the RS and CS

terminals at the PLC side with each other (leave the RS and CS terminals
at the NT-AL001 side open).

• When using the NT Link (1:N), cross-connect the RS and CS terminals at

the NT-AL001 and PLC sides.

If there is +5 V output at the PLC side, no external power supply is re-
quired for the NT-AL001.

C200HE-CPU32/42(-Z)E

C200HG-CPU33/43/53/63(-Z)E

C200HZ-CPU34/44/54/64(-Z)E

C200HX-CPU65-ZE

C200HX-CPU85-ZE

CV500-CPU01-EV1

CV1000-CPU01-EV1

CV2000-CPU01-EV1

CVM1-CPU01-EV2

CVM1-CPU11-EV2

CVM1-CPU21-EV2

SRM1-C02-V2

Shielding wire

(9-pin type)

NT-AL001 side

PLC side

(9-pin type)

1

6

5

9

1

6

5

9

When there is no +5 V output at the PLC side

When there is +5 V output at the PLC side

When using host link or NT Link (1:1)

When using NT Link (1:N)

Abbreviation Pin number

Pin number

Abbreviation

RS-232C
connector

Connector
hood

RS-232C
connector

Connector
hood

1

2

3

4

5

6

7

8

9

FG

SD

RD

RS

CS

+5V

SG

FG

SD

RD

RS

CS

+5V

SG

1

2

3

4

5

6

7

8

9

Advertising