Connecting to the Host’s RS-232C Port

Section 5-1

Wiring for a Memory Link Connection

Prepare the adapter cable while referring to the diagram shown below.

Since it is necessary to input a voltage of +5 V to the number 6 pin of NT-
AL001, supplying a voltage of 5 V from the host or an external voltage supply
for NT-AL001 is required.

5-1-3

1:N Connection between RS-422A/485 at the PT and RS-232C at
the Host

The connection method in which the RS-422A/485 ports of multiple NT631/
NT631Cs are connected to the RS-232C port of one host in a 1:N connection
is described here.

An RS-232C/RS-422A Adapter (NT-AL001) is used to convert between the
RS-232C and RS-422A/485 communications methods.

(9-pin type)

Shielding wire

No +5 V output is at the host side

A +5 V output is present at the host side

NT-AL001 side

Host side

1

6

5

9

Abbreviation Pin number

Abbreviation

RS-232C
connector

Connector
hood

RS-232C
connector

1

2

3

4

5

6

8

9

FG

SD

RD

RS

CS

+5V

SG

SD

RD

RS

CS

+5V

SG

Connector
hood

NT631/NT631C

Host Link Unit or CPU Unit

9-pin connector

9-pin connector

NT631/NT631C

NT631/NT631C

RS-422A/485 cable
(max. total length: 500 m)

Serial port B
(RS-422A/485, terminal block)

RS-422A terminal
block

RS-232C cable with
connectors

RS-232C/RS-422A
convertor unit
(NT-AL001)

CS/CJ-series PLC,
C200HX/HG/HE(-Z)E