243

Inspection and Cleaning

Section 7-4

Inspection Method

In normal environments, inspect the NT631/NT631C at intervals of between 6
months and a year. In environments that are extremely hot and humid, or very
dusty environments, shorten the inspection interval.

Items Required for The Inspection

Prepare the following items before starting the inspection.

• Screwdrivers (Phillips, flat head)

• Tester (or digital voltmeter)

• Industrial alcohol

• 100% cotton cloth

• Hygrometer (required in some cases)

• Thermometer (required in some cases)

• Synchroscope (required in some cases)

• Pen-writing oscilloscope (required in some cases)

Points Inspected

Inspect the following points to determine if there is any divergence from the
stated criteria. If there is, either improve the surrounding environment so that
the values fall within the stated range, or adjust the NT631/NT631C, for exam-
ple by re-tightening screws.

Note

1.

Do not disassemble for repairs or modification.

Point

Inspected

Inspection Details

Criterion

Inspection

Instrument

Power supply
voltage

Fluctuation in power supply terminal
voltage

Permissible voltage fluctuation range
20.4 to 26.4 VDC (24 VDC –15% to
+10%)

Tester

Ambient envi-
ronmental con-
ditions

Ambient temperature (temperature in
the operation panel)

0 to 50

°C

Thermometer

Ambient humidity (humidity in the
operation panel)

35% to 85% RH

Hygrometer

Presence/absence of dust

Dust must not be settled

Visual inspection

Mounting condi-
tions

Looseness of mounting brackets, etc.

To be no looseness

Phillips screwdriver

Connector connections of connecting
cable

To be fully inserted and locked, with no
looseness

Phillips screwdriver

Looseness of screws in external wir-
ing

To be no looseness

Phillips screwdriver

Conditions of external connecting
cables

Faults such as incipient disconnection

Visual inspection

Components
with limited lives

Brightness of the backlight
(NT631C only)

Must be sufficiently bright.

Backlight life:
(Under the normal range of ambient tem-
perature and humidity)

NT631C-ST141

@-EV2: Approx.

25,000 hours or longer
NT631C-ST151

@-EV2: Approx.

30,000 hours or longer
NT631C-ST152

@-EV2/ST153@-EV3:

Approx. 50,000 hours or longer
(Brightness setting is not available for
the NT631C-ST151/152

@-EV2/

ST153

@-EV3 and the backlight can-

not be replaced.)

Visual inspection