Omron Programmable Terminals NT631C User Manual

Page 77

Advertising
background image

60

Connecting to the RS-232C Port at the Host

Section 4-1

Connecting to CS-series Serial Communications Board

Serial Communications Board equipped with a RS-232C port for CS-series
CPU Units: CS1W-SCB21(-V1)/41(-V1) (See note.)

Note

Cannot be used with the CS1D-CPU65H/67H.

Allocation DM Area Settings for CPU Unit

Settings are written from the Programming Device (a Programming Console
or CX-Programmer) directly into the allocation DM area (system setting area)
of the CPU Unit. After the settings are written, they become effective by turn-
ing the power ON, restarting the Unit, restarting the communications port, or
execution of the STUP command.

In the following, the channel numbers of the allocation DM area and the set-
tings are shown.

Connecting to a CS/CJ-
series Serial
Communications Unit

CS/CJ-series Rack-mounting Unit:

CS1W-SCU21(-V1)

CJ1W-SCU21(-V1)/41(-V1)

Setting the Front-panel Switches

Set the unit number of the Serial Communications Unit by using the rotary
switch located on the front panel. Set each switch with a flat blade screwdriver
so that the values or symbols in the setting value window agree with the fol-
lowing.

DIP switches (inside the battery storage)

SYSMAC CS1G

PROGRAMMABLE CONTROLLER
CPU42

OPEN

OPEN

PERIPHERAL

PORT

BUSY

RUN

ERR/ALM

INH

PRPHL/COMM

MCPWR

• Set SW4 to ON (establishing communications in

accordance with PC Setup) when connecting the
NT631/NT631C to a peripheral port.

• Set SW5 to OFF (establishing communications

in accordance with PC Setup) when connecting
the NT631/NT631C to a peripheral port.

Peripheral port
This is used mainly for
connection to the
Programming Device.
(This also supports the
RS-232C unit connection.)

RS-232 port
This is used mainly for
connection to the RS-232C
unit.
(This also supports the
CX-Programmer.)

Allocation DM area (words)

Writing Value

Settings

Port 1

Port 2

DM32000

DM32010

8000

Host link mode, 2 stop bits, even parity, data
length 7 bits

DM32001

DM32011

0000

Communications speed 9600 bps.

0007

Communications speed 19200 bps.

DM32002

DM32012

0000

Transmit delay time 0 ms.

DM32003

DM32013

0000

No CTS control Unit No.0 for host link

Advertising
This manual is related to the following products: