Connecting to the Host’s RS-422A/485 Port

Section 5-2

Reference:

• There are no Serial Communications Boards for the C200HX/HG/HE(-Z)E

in which port B is the RS-422A/485 port.

• There are no Serial Communications Boards for the CQM1H in which port

1 is the RS-422A/485 port.

Setting the DIP Switches on a C200HX/HG/HE(-Z)E Communications
Board

Set the switches on a C200HX/HG/HE(-Z)E Communications Board as fol-
lows.

Switch 1:

(4-wire = RS-422A), or

(2-wire = RS-485)

Switch 2: ON (terminator ON = terminating resistance enabled).

Setting Switches on a CQM1H Serial Communications Board

Set the switches on a CQM1H Serial Communications Board as follows.

2-wire or 4-wire selector (WIRE):

(4-wire = RS-422A), or

(2-wire = RS-485)

Terminating resistance switch (TERM): ON (terminator ON = terminating

resistance enabled).

Connecting to CS-series Serial Communications Board

Serial Communications Board with RS-422A/485 port equipped for CS-series
CPU Unit:

CS1W-SCB41(-V1) (Port 2 is an RS-422A/485 port.)

Setting the Front Switches

2-wire or 4-wire selector (WIRE):

(4-wire = RS-422A), or

(2-wire = RS-485)

Terminating resistance switch (TERM): ON (terminator ON = terminating

resistance enabled).

4

2

4

2

Serial Communications Board
(Inner Board slot 1)

Terminator Switch (TERM)
Set to ON (right side)

Wire Selection Switch (WIRE)
When using RS-422A: Set to 4 (right side) for 4-wire type.
When using RS-485: Set to 2 (left side) for 2-wire type.

4

2