Omron Programmable Terminals NT631C User Manual

Page 71

Advertising
background image

54

Connecting to the RS-232C Port at the Host

Section 4-1

Setting The Front Switches

Connecting to a CPU Unit

CV-series and CVM1/CV-series (-EV

@) CPU Units

CV500-CPU01-EV1/CV1000-CPU01-EV1/CV2000-CPU01-EV1

CVM1-CPU01-EV2/CVM1-CPU11-EV2/CVM1-CPU21-EV2

PLC Setup

When connecting to a CVM1/CV-series CPU Unit, set the following communi-
cations conditions for the PLC Setup.

*1

Set the host link communications speed at 9600 bps or 19200 bps with the
memory switch at the NT631/NT631C. For details, refer to 6-7-2 Setting the
Host Link Method
(page 155)
.

Either set PLC Setup directly from a Programming Device (e.g. CX-Program-
mer), or transmit the PLC Setup made at a Programming Device to the CPU
Unit.

For details on the PLC Setup, refer to the SYSMAC CVM1/CV500/1000/2000
Operation Manual: Ladder Diagrams
(W202-E1-

@).

RS-232C

I/O port selector switch

RS-422A

• Unit # (SW3, SW4)

• Communications condition setting (DIP SW1)

Set this switch to OFF.

- Communications speed: 9600 bps
- Parity: Even
- Xon/Xoff control: Not executed
- Communications method: Full duplex
- Stop bits: 2 stop bits
- Data length: 7 bits

• I/O port selection (selector switch)

Set this to RS-232C.

• CTS selection (DIP SW2 and SW3)

Set SW2 or SW3 to ON. (Set this always to 0 V.)

Communications port 1
(RS-232C)

Communications port 2
(RS-232C/RS-422A)

When using communications port 2, set
these switches to 0.

To use communications port 1, set SW2. To
use communications port 2, set SW3.

Communications are executed in
accordance with the CPU Bus Unit system
settings made at the PLC. The initial values
for the system settings are as follows.

Item

Setting at Host

Communications speed

Set the same speed as set at the NT631/NT631C

(*1)

Stop bit

2 stop bits

Parity

Even

Data length

ASCII 7 bits

Unit #

00