125

Connecting to the Host’s RS-422A/485 Port

Section 5-2

Note

Before connecting or disconnecting cables between devices, make sure that
the power supply to all of the connected devices (NT631/NT631C, PLC, etc.)
is OFF.

Reference:

• The internal circuit of the NT631/NT631C is shown below.

• For details on setting the terminal resistance of the host, refer to Setting

methods for each type of the communications.

5-2-8

Handling the Shield on RS-422A/485 Cables

Perform the following procedures to connect, process the shield, and connect
to ground for communications systems using the RS-422A/485. Incorrect con-
nection may result in communications errors with the host.

Connecting the Ground Wire

The PT has a functional ground terminal (FG:

).

1,2,3...

1.

Ground according to Figure (a) for normal grounding.

• Connect the ground terminal (GR) of the devices to the functional ground

(FG: ).
Make sure that each signal line is grounded at only one point and ground
to 100

Ω max.

• Short the LG terminal of the PLC to the ground terminal (GR).

• Use a wire gauge of at least 2mm

2

for the ground wire.

• Refer to the manual for individual Communications Units for details on

proper wiring procedures.

2.

Do not ground the functional ground (FG:

) of the PT if it is mounted to

the same panel as devices that generate noise, such as motors or invert-
ers, as shown in Figure (b).

Preparing the Shield of RS-422A/485 Connectors

Always prepare RS-422A/485 cable shields properly. Otherwise, communica-
tions errors may occur with the host.

Ground only one end of the shield when connecting the ground terminal (GR)

of the devices to the functional ground (FG:

), and grounding each signal

line at only one point and to 100

Ω max, as shown in Figure (a).

Ground both ends of the shield when not grounding the functional ground

(FG:

) of the PT, as shown in Figure (b).

TRM-RDA

terminals

Function

Shorted

Terminal resistance is applied.

Short only at the NT631/NT631C connected to the end of an
RS-422A/485 cable.

Open

Terminal resistance is not applied.

Leave the terminals open when connecting an NT631/NT631C
anywhere other than at the end of the RS-422A/485 cable.

Terminal resistor (120

Ω)

RDB

RDA

TRM

+

-

Making a connection here inserts a terminator between
+ (RDB) and - (RDA).