1-1 the type of host and settings, The type of host and settings – Omron Programmable Terminals NT631C User Manual

Page 98

Advertising
background image

81

Connecting to the Host’s RS-232C Port

Section 5-1

Note

One end of the wire must always be connected to the host (PLC), and there
must be no branching. Branching will cause problems such as transmission
delays and communications failures.

Reference:

CS/CJ-series CPU Units cannot be connected with the 1:1 connection NT
Link method. Use the 1:N connection NT Link method (standard or high-
speed) instead to make the 1:1 connection. For details, refer to Using the NT
Link (1:N) Method
(page 65) or Using the High-speed NT Link (1:N) Method
(page 70).

5-1-1

The Type of Host and Settings

The using condition is the same as the connecting PT side RS-232C and the
host side RS-232C.
For the available type and settings of the host, refer to the pages listed below.

Settings at the RS-232C/
RS-422A Adapter (NT-
AL001)

When making a connection between RS-232C and RS-422A/485 ports using
an RS-232C/RS-422A Adapter, set the DIP switches on the NT-AL001 as fol-
lows.

PT

Host

RS-485 cable
(max. total length
500 m)

RS-232C
cable
(max. 2 m)

RS-232C/RS422A
convertor unit

NT631

NT631C

PLC

PLC

NT631

PLC

NT631C

NT631C

NT631

NT631

NT631

NT631

NT631

(At termination)

Relay terminal block

Relay terminal block

Max. 2 m

Example of Good Connection

Examples of Bad Connections

(Not at
termination)

(Not at
termination) (Not at

termination)

(At
termination)

Method

Reference

Host link

Host Link Method (page 48)

NT Link (1:1)

NT Link (1:1) method (page 61)

NT Link (1:N)

Using the NT Link (1:N) Method (page 65)

High-speed NT Link (1:N)

Using the High-speed NT Link (1:N) Method (page 70)

Memory link

Memory Link Method (page 73)

Advertising
This manual is related to the following products: