Connecting to the Host’s RS-422A/485 Port

Section 5-2

Setting the DIP Switches on a C200HX/HG/HE(-Z)E Communications
Board

Set the switches on a C200HX/HG/HE(-Z)E Communications Board as fol-
lows.

Switch 1:

(4-wire = RS-422A)

Switch 2: ON (terminator ON = terminating resistance enabled).

Setting Switches on a CQM1H Serial Communications Board

Set the switches on a CQM1H Serial Communications Board as follows.

2-wire or 4-wire selector (WIRE):

(4-wire = RS-422A)

Terminating resistance switch (TERM): ON (terminator ON = terminating

resistance enabled).

Using the NT Link (1:N)
Method

Compatible Host Units

The OMRON PLCs that can be connected using the RS-422A/485 NT Link
(1:N) method are the CS/CJ-series, C200HX/HG/HE(-Z)E, and CQM1H mod-
els only. A Serial Communications Board/Unit or a Communications Board
must be installed to make the connection.

Check the model and series of the PLC against the type of CPU Unit or com-
munications board before making the connections.

The hosts that can be connected to the RS-232C port of the NT631/NT631C
by the RS-422A NT Link (1:N) function via an Adapter are indicated in the
table below.

4

4

Serial Communications Board
(Inner Board slot 1)

Terminator Switch (TERM)
Set to ON (right side).

Wire Selection Switch (WIRE)
Set to 4 (right side).

PLC

Series

CPU Units with

Built-in NT Link

(1:1) Function

CPU Unit that becomes

connectable by installing a

Communications Board/Unit

Model Name

CS
Series

CS1G-CPU42/43/44/45-E(V1)

(*1)

CS1H-CPU63/64/65/66/67-E(V1)

(*1)

CS1G-CPU42H/43H/44H/45H

(*1)

CS1H-CPU63H/64H/65H/66H/67H

(*1)

CS1D-CPU65H/67H

(*2)

CS1G

CS1H

CS1D

CJ
Series

CJ1G-CPU44/45

(*3)

CJ1G-CPU42H/43H/44H/45H

(*3)

CJ1H-CPU65H/66H/67H

(*3)

CJ1M-CPU11/12/13/21/22/23

(*3)

CJ1G

CJ1H

CJ1M