Omron Programmable Terminals NT631C User Manual

Page 119

Advertising
background image

102

Connecting to the Host’s RS-422A/485 Port

Section 5-2

Setting the Front Switches

C200HX/HG/HE(-Z)E, CPM1, CPM2A, CPM2C, CQM1H, or SRM1

The connection method depends upon the model of PLC being used, as
shown in the following table.

Reference:

• There are no Communications Boards for the C200HX/HG/HE(-Z)E in

which port B is the RS-422A port.

• There are no Serial Communications Boards for the CQM1H in which port

1 is the RS-422A port.

PLC model

Connection method

C200HX/HG/HE(-Z)E

Connect to the RS-422A port (port A) on a Communications
Board.

CQM1H

Connect to the RS-422A port (port 2) on a Serial Communi-
cations Board.

CPM1

Connect to the peripheral port through a CPM1-CIF11 RS-
422A Adapter.

CPM2A, SRM1

Connect to the peripheral port through a CPM1-CIF11 RS-
422A Adapter.

CPM2C

Connect to the peripheral port (on a CPM2C-CN111 or
CS1W-CN114 Connecting Cable) through a CPM1-CIF11
RS-422A Adapter.

(The CPM2C-CN111 splits the Unit’s Communications Port
into a RS-232C port and a peripheral port.)

I/O port selector switch

RS-422A

Set this to RS-422A.

• Host link default value settings

(DIP SW4)

Note

RS-232C

• Terminator setting (DIP SW6)

Set this switch to ON.
(Set terminator ON.)

• Communications type setting (DIP SW3)

Set SW3 to OFF.
(for host link communications)

• Host link communications method

selection (selector switch)

To effect the existing DIP switch
settings, set SW4 to ON.

To effect the values set in the PLC
Setup, set SW4 to OFF.

For CPU Units manufactured before or
during June 1995 (lot No.

@@65), the

existing DIP switch settings differ from
the PLC Setup default values as follows.

- Existing DIP switch settings:
2,400 bps, 1 stop bit, even parity, 7 bit

data length

- PLC Setup default values:

9,600 bps, 2 stop bits, even parity, 7
bit data length

For CPU Units manufactured from July
1995 onward (lot No.

@@75), the

stipulated values in the DIP switch
settings also are 9600 bps and 2 stop bits

Advertising