Setting the rear switches – Omron Programmable Terminals NT631C User Manual

Page 115

Advertising
background image

98

Connecting to the Host’s RS-422A/485 Port

Section 5-2

Setting the Rear Switches

I/O port

RS-422A
RS-232C

Synchronization

Internal
External

OFF

ON

CTS

0 V

External

• I/O port selection (selector switch)

Set this to RS-422A.

• Unit # (DIP SW1)

Set SW1-1 to SW1-5 to OFF (0).

• Synchronization (selector switch)

Set this to Internal.

• Communications speed

(DIP SW2-1 to SW2-4)

• 1-to-1/1-to-N selection (DIP SW2-6)

Set SW2-6 to OFF (0) (1-to-N).

• Instruction level (DIP SW2-7, SW2-8)

Set these switches to ON (1).

(Levels 1, 2, and 3 are enabled.)

• CTS selection (selector switch)

Set this always to 0 V (ON).

Terminator

• Terminator setting (selector switch)

Set this switch to ON.

ON

ON

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

SW1

SW2

Set these switches to 1010 to select
9600 bps.
(0: OFF 1: ON)

Set these switches to 0010 to select
19200 bps.

Advertising