51

Connecting to the RS-232C Port at the Host

Section 4-1

Setting the Rear Switches

C1000H(F)/C2000H Rack-mounting Unit: 3G2A5-LK201-EV1

Setting the Front Switches

Setting the Rear Switches

ON

1

CTS selector switch

External

0 V (ON)

• 1-to-1/1-to-N selection (DIP switch)

Set #3 to ON.

• CTS selection (selector switch)

Set this always to 0 V (ON).

2

3

4

• Mode control (key switch)

Set this to host link.

Local

Host

ON

ON

SW1

SW2

1

2

3

4

5

6

7

8

I/O port

RS-422A
RS-232C

Synchronization

Internal
External

Terminator

OFF
ON

CTS

0 V

External

• I/O port selection (selector switch)

Set this to RS-232C.

• Unit # (DIP SW1)

Set SW1-1 to SW1-5 to OFF (0).

• Synchronization (selector switch)

Set this to Internal.

• Communications speed

(DIP SW2-1 to SW2-4)

• 1-to-1/1-to-N selection (DIP SW2-6)

Set SW2-6 to OFF (0) (1-to-N).

• Instruction level (DIP SW2-7, SW2-8)

Set these switches to ON (1).
(Levels 1, 2, and 3 are enabled.)

• CTS selection (selector switch)

Set this always to 0 V (ON).

1

2

3

4

5

6

7

8

Set these switches to 0010 to select
19,200 bps.

Set these switches to 1010 to select
9,600 bps.(0: OFF 1: ON)