Omron Programmable Terminals NT631C User Manual

Page 45

Advertising
background image

28

Method for Connection to the Host

Section 2-1

❍: Connection possible

×: Connection not possible

• The RS-232C/RS-422A adapter (NT-AL001) requires +5 V, 150 mA at pin

6 of the RS-232C connector. Check the signals of the RS-232C connector
at the host.

• +5 V is not output from serial port B of the NT631/NT631C. When con-

necting an NT-AL001 at serial port B, a separate power supply is required
for the NT-AL001.

• The cable of an NT-AL001 cannot be connected or disconnected while the

power is ON. Always connect or disconnect the cable while the power
supply from the RS-232C cable is OFF (while the host power supply is
OFF).

• NT Link (1:N) connection is possible even when RS-232C is used at the

NT631/NT631C side for communications with the host, but in this case
one NT-AL001 Adapter is required for each NT631/NT631C. In this case,
it is convenient to use serial port A of the NT631/NT631C. +5 V is not out-
put from serial port B.

Communica-

tions Type at

PT

Communica-

tions Type at

Host

Usable Connection Method

Usable Communications

Method

Details

Host

link

NT

Link
(1:1)

NT

Link

(1:N)

Mem-

ory

link

RS-485

RS-232C

Ч

Ч

Ч

page 82

Ч

Ч

Ч

page 86

RS-485

Ч

Ч

Ч

page 118

Ч

Ч

Ч

page 121

1:1 connection via a convertor unit

PT

Host

Convertor unit
(NT-AL001)

RS-485
(max. 500 m)

RS-232C
(max. 2 m)

1:N connection via a convertor unit

PT

Host

Convertor unit
(NT-AL001)

RS-485
(total length 500 m)

RS-232C
(max. 2 m)

Direct 1:1 connection

PT

Host

RS-485 (max. 500 m)

1:N connection

PT

Host

RS-485 (total length 500 m)