Connecting to the RS-232C Port at the Host

Section 4-1

C1000H/C2000H Rack-mounting Unit: C500-LK203

Setting the Rear Switches

C200H/C1000H/C2000H CPU-mounting Unit: 3G2A6-LK201-EV1

Setting the Rear Switches

ON

ON

SW1

SW2

I/O port

RS-422A
RS-232C

Synchronization

Internal
External

Terminator

OFF

ON

CTS

0 V

External

• I/O port selection (selector switch)

Set this to RS-232C.

• Synchronization (selector switch)

Set this to Internal.

• Communications speed

(DIP SW2-1 to SW2-4)

• 1-to-1/1-to-N selection (DIP SW2-6)

Set SW2-6 to OFF (0) (1-to-N).

• Instruction level (DIP SW2-7, SW2-8)

Set these switches to ON (1).
(Levels 1, 2, and 3 are enabled.)

5 V supply

ON
OFF

• Unit #, parity, and transfer code

(DIP SW1-1 to SW1-7)

Set SW1-1 to SW1-7 to OFF (0).

• CTS selection (selector switch)

Set this always to 0 V (ON).

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

Set these switches to 0010 to select
19,200 bps.

Set these switches to 1010 to select
9,600 bps.(0: OFF 1: ON)

SW1

SW2

SW3

• Unit #, parity, and transfer code

(DIP SW1-1 to SW1-5)

Set SW1-1 to SW1-5 to OFF (0).

• Communications speed (DIP SW2-1 to SW2-4)

Set these switches to 0010 to select 19200 bps.
Set these switches to 1010 to select 9600 bps.
(0: OFF 1: ON)

• 1-to-1/1-to-N selection (DIP SW2-6)

Set SW2-6 to OFF (0) (1-to-N).

• Instruction level (DIP SW2-7, SW2-8)

Set these switches to ON (1).
(Levels 1, 2, and 3 are enabled.)

• CTS selection (DIP SW3-1 and SW3-2)

Set SW3-1 to ON (1), and SW3-2 to OFF (0).
(Set this always to 0V.)

• Synchronization (DIP SW3-3 to SW3-6)

* Parity is fixed at Even Parity. Transfer code is

fixed at ASCII 7 data bits and 2 stop bits.

Set SW3-3, SW3-5, and SW3-6 to ON (1), and
SW3-4 to OFF (0). (Set these to Internal.)