271

Appendix F

Making the Cable for Connecting a PLC

Refer to the following when making a cable for connecting the Support Tool.

Assembly of Connecting Cables

Wiring should be carried out in one of the following ways, depending on the type of RS-232C connector.

25-pin Connector

Note Connect a shielding wire to the connector hood of the connectors both at the personal computer end

and the PT end.

Use the following recommended products when making the connecting cable.

9-pin Connector

Note Connect a shielding wire to the connector hood of the connectors both at the personal computer end

and the PT end.

SD

RD

RS

CS

SG

FG

Personal computer

Connector for peripheral devices on PT

Shielding wire

Connector hood

2

3

4

5

7

1

SD

RD

RS

CS

SG

2

3

4

5

9

Connector hood

Name

Model

Remarks

Connector

XM2D-2501

25-pin, made by OMRON, for personal computer side

XM2A-0901

9-pin, made by OMRON, for PT side

Connector hood

XM2S-2511

25-pin, made by OMRON, for personal computer side

XM2S-0911

9-pin, made by OMRON, for PT side

Cable

AWG28

×5P IFVV-SB

Multi-core shielded cable, made by Fujikura Ltd.

CA-MA-VV-SB 5P

×28AWG

Multi-core shielded cable, made by Hitachi Cable, Ltd.

RD

SD

RS

CS

SG

Personal computer

Connector for peripheral devices on PT

Shielding wire

Connector hood

2

3

7

8

5

SD

RD

RS

CS

SG

2

3

4

5

9

Connector hood