A5.5.2 Determining the Output Value

The value of OUT.Value is determined as follows:

● For counting up

OUT = integration start value (0) + Total

● For counting down

OUT = integration start value (TOTAL_SP) -
Total

Total: Total of integrated values. This value
is retained even if INTEG_TYPE is changed
during integration (in AUTO).

OUT_TRIP(#14):0

OUT_PTRIP(#15):0

OUT_TRIP(#14):1

OUT_PTRIP(#15):1

Counting up starting from 0

‡)RUFRXQWLQJXS

PRE_TRIP(#31)

OUT_TRIP(#14):0

OUT_PTRIP(#15):0

OUT_TRIP(#14):0

OUT_PTRIP(#15):1

OUT_TRIP(#14):1

OUT_PTRIP(#15):1

‡)RUFRXQWLQJGRZQ

Counting down starting from TOTAL_SP

PRE_TRIP(#31)

0

0

TOTAL_SP(#7)

TOTAL_SP(#7)

FA0505.ai

OUT_TRIP(#14):0

OUT_PTRIP(#15):1

If OUT is rewritten in the MAN mode, integration
starts with the value rewritten in MAN mode after
the mode was returned to AUTO.
The values in OUT_TRIP and OUT_PTRIP are
determined according to the correlation between
OUT and TOTAL_SP/PRE_TRIP.

For counting up, the OUT value is as follows:

● OUT < TOTAL_SP - PRE_TRIP

OUT_TRIP = 0, COUT_PTRIP = 0

● TOTAL_SP - PRE_TRIP <= OUT < TOTAL_

SP
OUT_TRIP = 0, COUT_PTRIP = 1

● TOTAL_SP <= OUT

OUT_TRIP = 1, COUT_PTRIP = 1

For counting down, the OUT value is as follows:

● PRE_TRIP < OUT

OUT_TRIP = 0, COUT_PTRIP = 0

● 0 < OUT <= PRE_TRIP

OUT_TRIP = 0, COUT_PTRIP = 1

● OUT <= 0

OUT_TRIP = 1, COUT_PTRIP = 1

Note that the given conditions do not apply to the
following cases:

If INTEG_TYPE is 5, 6, or 7, OUT_TRIP and
OUT_PTRIP always output “0.”

• If INTEG_TYPE is 1 or 3, occurrence of

AutoRESET (reset caused if the threshold is
exceeded) causes OUT_TRIP to hold “1” for
fi ve seconds.

<APPENDIX 5. INTEGRATOR (IT) BLOCK>

A5-7

IM 01F06F00-01EN