<6. EXPLANATION OF BASIC ITEMS>

6-2

IM 01F06F00-01EN

6.2 Transducer Block Parameters

The transducer block sets functions specifi c to the
fl ow rate measurement of the digitalYEWFLO. For
each block parameter in digitalYEWFLO, refer
to APPENDIX 1 “LIST OF PARAMETERS FOR
EACH BLOCK OF digitalYEWFLO.” The following
describes important parameters and how to set
them.
For the METHOD of TR block, refer to APPENDIX
10.1 “Transducer Block”.

(1) Mandatory Parameter Setting for

Transducer Block

After setting parameters of the transducer block,

set up XD_SCALE of the AI1 block (and of the
AI2 block as appropriate).

Table 6.1 shows the parameters that must be

set (in order of the relative index sequentially)
depending on the operation conditions.

Table 6.1

Mandatory Parameter Setting for Transducer Block Depending on Operation Conditions

Relative Index

Parameter

Name

Operation Conditions

47

SENSOR_
STATUS

1 =
Standard

1 =
Standard

2 = Built-in
Temp.
Sensor

2 = Built-in
Temp.
Sensor

2 = Built-in
Temp.
Sensor

2 = Built-in
Temp.
Sensor

2 = Built-in
Temp.
Sensor

2 = Built-in
Temp.
Sensor

48

THERMOMETER_
FUNCTION

1 = Monitor
only; or
6 = Not use

1 = Monitor
only; or
6 = Not use

2 =
Saturated
steam

3 =
Superheat
steam

4 = GAS:
STD/Normal

5 = LIQUID:
Mass

49 FLUID_TYPE

1 = LIQUID:
Volume;

2 =
GAS/
STEAM:
Volume;

3 =
LIQUID:
Mass or

4 =
GAS/
STEAM:
Mass

5 = GAS:
STD/Normal

1 = LIQUID:
Volume;

2 =
GAS/
STEAM:
Volume;

3 =
LIQUID:
Mass or

4 =
GAS/
STEAM:
Mass

5 = GAS:
STD/Normal

Mandatory

50

TEMPERATURE_
UNIT

51 PROCESS_TEMP

52 BASE_TEMP

53 DENSITY_UNIT

54

PROCESS_
DENSITY

55 BASE_DENSITY

56

PRESSURE_
UNIT

57

PROCESS_
PRESSURE

58

BASE_
PRESSURE

59 DEVIATION

62

FIRST_TEMP_
COEF

63

SECOND_TEMP_
COEF