APPENDIX 5. INTEGRATOR (IT) BLOCK

IN_1: Block input 1 (value and status)
IN_2: Block input 2 (value and status)
REV_FLOW1: Indicates whether the sign of IN_1 is
reversed. It is a discrete signal.
REV_FLOW2: Indicates whether the sign of IN_2 is
reversed. It is a discrete signal.
RESET_IN: Resets the integrated values. It is a
discrete signal.
RESET_CONFIRM: Reset confi rmation input. It is a
discrete signal.
OUT: Block output (value and status)
OUT_PTRIP: Set if the target value exceeds PRE_
TRIP. It is a discrete signal.
OUT_TRIP: Set if the target value exceeds TOTAL_
SP (or 0). It is a discrete signal.

The Integrator (IT) block adds two main inputs and
integrates them for output. The block compares the
integrated or accumulated value to TOTAL_SP and
PRE_TRIP and generates discrete output signals
OUT_TRIP or OUT_PTRIP when the limits are
reached.
The output is as represented by the following
equation (for counting upward and rate conversion).

OUT.Value = Integration start value + Total
Total = Total + Current Integral
Current Integral = (x + y) ×

∆t

x: IN_1 value whose unit has been converted
y: IN_2 value whose unit has been converted
∆t: block execution period

A5.1 Schematic Diagram of Integrator Block

The following shows the schematic diagram of the Integrator block.

OUT

IN_1

RESET_IN

REV_FLOW1

–1

TIME_UNIT2

IN_2

REV_FLOW2

PULSE_VAL2

–1

UNIT_CONV

OP_CMD_INT

(RESET)

INTEG_OPTS

(CARRY)

Reverse

Forward

Forward

OUT_PTRIP

OUT_TRIP

INTEG_OPTS
(FLOW TYPE)

Add

Compare

Compare

TOTAL / RTOTAL

Integrate

INTEG_TYPE

INTEG_OPTS (QUALITY)

GOOD_LIM

UNCERT_LIM

CLOCK_PER

N_RESET

MAN

MAN

MAN

Convert Rate

Convert Accum

Convert Rate

Convert Accum

TOTAL_SP

PRE_TRIP

INTEG_OPTS
(INPUT TYPE)

PULSE_VAL1

TIME_UNIT1

INTEG_OPTS
(INPUT TYPE)

RESET_CONFIRM

Reverse

FA0501.ai

Figure A5.1 Integrator Block

The Integrator block is classifi ed into the following
fi ve sections for each function:

• Input process section: Determines the

input value status, converts the rate and
accumulation, and determines the input fl ow
direction.

• Adder: Adds the two inputs.
• Integrator: Integrates the result of the adder into

the integrated value.

• Output process section: Determines the status

and value of each output parameter.

• Reset process section: Resets the integrated

values.