Yokogawa digitalYEWFLO (DY-FF) User Manual

Page 34

Advertising
background image

<6. EXPLANATION OF BASIC ITEMS>

6-3

IM 01F06F00-01EN

(2) Explanations of Parameters

1) PRIMARY_VALUE_TYPE (Relative Index 13)
Indicates the type of the measured item

represented by PRIMARY_VALUE. For the
digitalYEWFLO, the value of PRIMARY_
VALUE_TYPE is 100 and 101 as follows:

100 = Mass fl ow
101 = Volumetric fl ow
65535 = Other
Default: 101 (Volumetric fl ow)
2) PRIMARY_VALUE_FTIME (Relative Index 30)
Defi nes the damping time constant for

the fl ow rate to be input to the fl ow rate
calculation.

Setting range: 0 to 99 (seconds)
Default: 4 (seconds)
3) THERMOMETER_FUNCTION (Relative Index 48)
Determines the use of the temperature

monitoring function for a model with the MV
option.

1 = Monitor only
2 = Saturated steam
3 = Superheat steam
4 = Gas: STD/Normal
5 = LIQUID: Mass
6 = Not use
Default: 1 (= Monitor only)
4) FLUID_TYPE (Relative Index 49)
Selects the type of process fl uid to be

measured.

1 = LIQUID: Volume
2 = Gas/Steam: Volume
3 = LIQUID: Mass
4 = Gas/Steam: Mass
5 = Gas: Std/Normal
Default: 1 (= LIQUID: Volume)
5) TEMPERATURE_UNIT (Relative Index 50)
Selects the unit of temperature.
Setting range: 1001 (=

C), 1002 (= F)

Default: 1001 (=

C)

6) PROCESS_TEMP (Relative Index 51)
Sets the normal operating temperature.
Setting range: -999.9 to 999.9
Unit: As selected in TEMP_UNIT
Default: 15.0
7) BASE_TEMP (Relative Index 52)
Sets the temperature under the standard

conditions.

Setting range: -999.9 to 999.9
Unit: As selected in TEMP_UNIT
Default: 15.0

8) DENSITY_UNIT (Relative Index 53)
Selects the unit of density.
Setting range: 1097 (=kg/m

3

)

Default: 1097 (= kg/m

3

)

9) PROCESS_DENSITY (Relative Index 54)
Selects the density under the normal

operating conditions.

Setting range: 0.00001 to 32000
Unit: As selected in DENSITY_UNIT
Default: 1024.0
10) BASE_DENSITY (Relative Index 55)
Sets the density under the standard

conditions.

Setting range: 0.00001 to 32000
Unit: As selected in DENSITY_UNIT
Default: 1024.0
11) PRESSURE_UNIT (Relative Index 56)
Selects the unit of pressure.
Setting range: 1545 (= MPaa) or 1547 (= kPaa)
Default: 1545 (= MPaa)
12) PROCESS_PRESSURE (Relative Index 57)
Sets the absolute pressure under the normal

operating conditions.

Setting range: 0.00001 to 32000
Unit: As selected in PRESSURE_UNIT
Default:

0.1013

13) BASE_PRESSURE (Relative Index 58)
Sets the absolute pressure under the

standard conditions.

Setting range: 0.00001 to 32000
Unit: As selected in PRESSURE_UNIT
Default:

0.1013

14) DEVIATION (Relative Index 59)
Sets the deviation factor of the process fl uid.
Setting range: 0.001 to 10.0
Default: 1.0 (nondimensional number)
15) SECONDARY_VALUE_FTIME (Relative Index 60)
Sets the damping factor for temperature

measurement (for a model with the MV
option).

Setting range: 0 to 99
Unit: s (seconds)
Default: 4 (seconds)
16) SIZE_SELECT (Relative Index 64)
Selects

the

fl owmeter size.

Setting

range:

1 = 15 mm (1/2 in.) 2 = 25 mm (1 in.)
3 = 40 mm (1.5 in.) 4 = 50 mm (2 in.)
5 = 80 mm (3 in.)

6 = 100 mm (4 in.)

7 = 150 mm (6 in.) 8 = 200 mm (8 in.)
9 = 250 mm (10 in.) 10 = 300 mm (12 in.)
11 = 400 mm (16 in.)
Default: 2 (= 25 mm (1 in.))

Advertising