A12-4 – Yokogawa digitalYEWFLO (DY-FF) User Manual

Page 165

Advertising
background image

<APPENDIX 12. DEVICEVIEWER WINDOW EXECUTED FROM PRM (Plant Resource Manager)>

A12-4

IM 01F06F00-01EN

Alarm item

Alarm No.

Description

Parameter

DI2 in O/S Mode
(AL-26)

AL-26

DI2 Block is in O/S mode. (AL-26)
[Remedy]: Change the DI2 Block Mode. Target (DI2.MODE_BLK.Target) to Auto or other
mode.
In addition, check that RB Block Mode. Actual (RB.MODE_BLK.Actual) is set to Auto
mode.

RS DEVICE_
STATUS_3 bit21

DI2 in Man Mode
(AL-71)

AL-71

DI2 Block is in Manual mode. (AL-71)
[Remedy]: Change the DI2 Block Mode. Target (DI2.MODE_BLK.Target) to Auto or other
mode.

RS DEVICE_
STATUS_3 bit6

DI2 Simulation
Active (AL-72)

AL-72

DI2 Block is in simulation mode. (AL-72)
[Remedy]: Change the DI2 Simulation Enable/Disable (DI2.SIMULATE_ENABLE) to
Disabled.

RS DEVICE_
STATUS_3 bit5

DI2 Not
Scheduled
(AL-73)

AL-73

DI2 Block is not scheduled. (AL-73)
[Remedy]: Make a schedule of DI2 Block.

RS DEVICE_
STATUS_3 bit4

Simulation
Switch ON

-

Software or hardware simulation switch is ON.
[Remedy]: Change the value of RB Sim Enable Message (RB.SIM_ENABLE_MSG) or
turn off the hardware simulation switch.

RS DEVICE_
STATUS_1 bit23

Table A12.5 Others

Alarm item

Alarm No.

Description

Parameter

PID in O/S Mode
(AL-27)

AL-27

PID Block is in O/S mode. (AL-27)
[Remedy]: Change the PID Block Mode. Target (PID.MODE_BLK.Target) to Auto or other
mode.
In addition, check that RB Block Mode. Actual (RB.MODE_BLK.Actual) is set to Auto
mode.

RS DEVICE_
STATUS_3 bit20

PID in Bypass
Mode (AL-74)

AL-74

PID Block is in Bypass mode. (AL-27)
[Remedy]: Change the value of PID Bypass (PID.BYPASS) to OFF.

RS DEVICE_
STATUS_3 bit2

IT in O/S Mode
(AL-29)

AL-29

IT Block is in O/S mode. (AL-29)
[Remedy]: Change the IT Block Mode. Target (IT.MODE_BLK.Target) to Auto or other
mode.
In addition, check that RB Block Mode. Actual (RB.MODE_BLK.Actual) is set to Auto
mode.

RS DEVICE_
STATUS_5 bit26

IT in Man Mode
(AL-80)

AL-80

IT Block is in Manual mode. (AL-80)
[Remedy]: Change the IT Block Mode. Target (IT.MODE_BLK.Target) to Auto or other
mode.

RS DEVICE_
STATUS_5 bit19

IT Not Scheduled
(AL-81)

AL-81

IT Block is not scheduled. (AL-81)
[Remedy]: Make a schedule of IT Block.

RS DEVICE_
STATUS_5 bit18

IT Total Backup
Err (AL-82)

AL-82

IT Total backup failed. Last IT Output.Value (IT.OUT.Value) could not saved. (AL-82)
[Remedy]: Contact the nearest offi ce or service center.

RS DEVICE_
STATUS_5 bit17

IT Conf. Err
(AL-83)

AL-83

IT Clock Period (IT.CLOCK_PER) is smaller than IT Period of Execution (IT.
EXECUTION_PERIOD). (AL-83)
[Remedy]: Change the value as IT Clock Period (IT.CLOCK_PER) is larger than IT
Period of Execution (IT.EXECUTION_PERIOD).

RS DEVICE_
STATUS_5 bit16

AR in O/S Mode
(AL-30)

AL-30

AR Block is in O/S mode. (AL-30)
[Remedy]: Change the AR Block Mode. Target (AR.MODE_BLK.Target) to Auto or other
mode.
In addition, check that RB Block Mode. Actual (RB.MODE_BLK.Actual) is set to Auto
mode.

RS DEVICE_
STATUS_5 bit25

AR in Man Mode
(AL-84)

AL-84

AR Block is in Manual mode. (AL-84)
[Remedy]: Change the AR Block Mode. Target (AR.MODE_BLK.Target) to Auto or other
mode.

RS DEVICE_
STATUS_5 bit14

AR Not
Scheduled
(AL-85)

AL-85

AR Block is not scheduled. (AL-85)
[Remedy]: Make a schedule of AR Block.

RS DEVICE_
STATUS_5 bit13

AR Range Conf.
Err (AL-86)

AL-86

AR Range High (AR.RANGE_HI) is smaller than AR Range Low (AR.RANGE_LOW).
(AL-86)
[Remedy]: Change the value as AR Range High (AR.RANGE_HI) is larger than AR
Range Low (AR.RANGE_LO).

RS DEVICE_
STATUS_5 bit12

AR Temp. IN
Over Range
(AL-87)

AL-87

AR Input1 (AR.IN_1) is over range. (AL-87)
[Remedy]: This case is out of specifi cation. Refer to IM, Check the engineering setting or
AR Temperature Unit (AR.AR_TEMPERATURE_UNIT).

RS DEVICE_
STATUS_5 bit11

AR Press IN
Over Range
(AL-88)

AL-88

AR Input2 (AR.IN_2) is over range. (AL-88)
[Remedy]: This case is out of specifi cation. Refer to IM, Check the engineering setting or
AR Pressure Unit (AR.AR_PRESSURE_UNIT) and AR Bias Input2 (AR.BIAS_IN_2).

RS DEVICE_
STATUS_5 bit10

Advertising