<APPENDIX 1. LIST OF PARAMETERS FOR EACH BLOCK OF digitalYEWFLO>

A1-2

IM 01F06F00-01EN

Relative

Index

Index

Parameter Name

Factory Default

Write

Mode

Explanation

18

1018

FEATURE_SEL

0x000a
(Soft write lock
supported
Report supported)

AUTO

Used to select resource block options.

Bit0: Scheduled
Bit1: Event driven
Bit2: Manufacturer specifi ed

19

1019

CYCLE_TYPE

0x0001(Scheduled)

Identifi es the block execution methods available for this
resource.

20

1020

CYCLE_SEL

0x0001(Scheduled)

AUTO

Used to select the block execution method for this
resource.

21

1021

MIN_CYCLE_T

3200

Time duration of the shortest cycle interval of which the
resource is capable.

22

1022

MEMORY_SIZE

0

Available confi guration memory in the empty resource. To
be checked before attempting a download.

23

1023

NV_CYCLE_T

0

Interval between writing copies of NV parameters to non-
volatile memory. Zero means never.

24

1024

FREE_SPACE

0

Percent of memory available for further confi guration.
digitalYEWFLO has zero which means a preconfi gured
resource.

25

1025

FREE_TIME

0

Percent of the block processing time that is free to process
additional blocks. Supported only with PID function.

26

1026

SHED_RCAS

640000 (20 s)

AUTO

Time duration at which to give up on computer writes to
function block RCas locations. Supported only with PID
function.

27

1027

SHED_ROUT

640000 (20 s)

AUTO

Time duration at which to give up on computer writes to
function block ROut locations. Supported only with PID
function.

28

1028

FAULT_STATE

1

Condition set by loss of communication to an output block,
failure promoted to an output block or a physical contact.
When fail-safe condition is set, Then output function blocks
will perform their FSAFE actions. Supported only with PID
function.

29

1029

SET_FSTATE

1 (OFF)

AUTO

Allows the fail-safe condition to be manually initiated by
selecting Set. Supported only with PID function.

30

1030

CLR_FSTATE

1 (OFF)

AUTO

Writing a Clear to this parameter will clear the device
fail-safe state if the fi eld condition, if any, has cleared.
Supported only with PID function.

31

1031

MAX_NOTIFY

3

Maximum number of unconfi rmed notify messages
possible.

32

1032

LIM_NOTIFY

3

AUTO

Maximum number of unconfi rmed alert notify messages
allowed.

33

1033

CONFIRM_TIME

640000 (20 s)

AUTO

The minimum time between retries of alert reports.

34

1034

WRITE_LOCK

1 (Not locked)

AUTO

If set, no writes from anywhere are allowed, except to clear
WRITE_LOCK. Block inputs will continue to be updated.

1: Not locked, 2: Locked

35

1035

UPDATE_EVT

This alert is generated by any change to the static data.

36

1036

BLOCK_ALM

The block alarm is used for all confi guration, hardware,
connection failure or system problems in the block. The
cause of the alert is entered in the subcode fi eld. The
fi rst alert to become active will set the Active status in
the Status attribute. As soon as the Unreported status
is cleared by the alert reporting task, another block alert
may be reported without clearing the Active status, if the
subcode has changed.

37

1037

ALARM_SUM

The current alert status, unacknowledged states,
unreported states, and disabled states of the alarms
associated with the function block.

38

1038

ACK_OPTION

0xffff

AUTO

39

1039

WRITE_PRI

0

AUTO

Priority of the alarm generated by clearing the write lock.
0, 1, 3 to 15

40

1040

WRITE_ALM

This alert is generated if the write lock parameter is
cleared.

41

1041

ITK_VER

5

Version number of interoperability test by Fieldbus
Foundation applied to digitalYEWFLO.

42

1042

SOFT_REV

digitalYEWFLO software revision number.