<4. GETTING STARTED>

4-1

IM 01F06F00-01EN

4. GETTING

STARTED

Fieldbus is fully dependent upon digital
communication protocol and differs in operation
from conventional 4 to 20 mA transmission
and the BRAIN communication protocol. It is
recommended that novice users use fi eldbus
devices in accordance with the procedures
described in this section. The procedures assume
that fi eldbus devices will be set up on a bench or in
an instrument shop.

4.1 Connection of Devices

The following instruments are required for use with
Fieldbus devices:

• Power supply:

Fieldbus requires a dedicated power supply. It

is recommended that current capacity be well
over the total value of the maximum current
consumed by all devices (including the host).
Conventional DC current cannot be used as is.

• Terminator:

Fieldbus requires two terminators. Refer to

the supplier for details of terminators that are
attached to the host.

• Field devices:

Connect your Fieldbus communication type

digitalYEWFLO to a fi eldbus. Two or more
digitalYEWFLOs and other fi eld devices can be
connected. For the terminal assignment on the
digitalYEWFLO, see Table 4.1.

Table 4.1

Terminal Connection for

digitalYEWFLO

Terminal Symbols

Description

SUPPLY +
SUPPLY –

Fieldbus Communication Signal
Terminals

Grounding Terminal

• Host:

Used for accessing fi eld devices. A

dedicated host (such as DCS) is used for
an instrumentation line while dedicated
communication tools are used for experimental
purposes. For operation of the host, refer to the
instruction manual for each host. No other details
on the host are given in this manual.

• Cable:

Used for connecting devices. Refer to “Fieldbus

Technical Information” (TI 38K03A01-01E) for
details of instrumentation cabling. For laboratory
or other experimental use, a twisted pair cable
two to three meters in length with a cross section
of 0.9 mm

2

or more and a cycle period of within

5 cm (2 inches) may be used. Termination
processing depends on the type of device being
deployed. For the digitalYEWFLO, use terminal
lugs applicable to M4 screw terminals. Some
hosts require a connector.

Refer to Yokogawa when making arrangements to
purchase the recommended equipment.
Connect the devices as shown in Figure 4.1.
Connect the terminators at both ends of the
trunk, with a minimum length of the spur laid for
connection.
The polarity of signal and power must be
maintained.

digitalYEWFLO

Fieldbus power
supply

Terminator

Terminator

HOST

F0401.ai

+

Figure 4.1

Device Connection

IMPORTANT

Connecting a Fieldbus confi guration tool
to a loop with its existing host may cause
communication data scrambling resulting
in a functional disorder or a system failure.
Disconnect the relevant control loop from the bus
if necessary.