<APPENDIX 12. DEVICEVIEWER WINDOW EXECUTED FROM PRM (Plant Resource Manager)>

A12-5

IM 01F06F00-01EN

Alarm item

Alarm No.

Description

Parameter

AR Flow IN
NotConnected
(AL-89)

AL-89

AR Input (AR.IN) is not connected to the volumetric fl ow. (AL-89)
[Remedy]: Connect the volumetric fl ow data into AR Input (AR.IN).

RS DEVICE_
STATUS_5 bit9

AR Temp. IN
NotConnected
(AL-90)

AL-90

AR Input1 (AR.IN_1) is not connected to the temperature. (AL-90)
[Remedy]: Connect the temperature data into AR Input1 (AR.IN_1).

RS DEVICE_
STATUS_5 bit8

AR Press IN
NotConnected
(AL-91)

AL-91

AR Input2 (AR.IN_2) is not connected to the pressure. (AL-91)
[Remedy]: Connect the pressure data into AR Input2 (AR.IN_2).

RS DEVICE_
STATUS_5 bit7

AR Comp. Coef.
Conf. Err (AL-92)

AL-92

AR Compensation Coeffi cient (AR.AR_FLOW_CONFIG.Element) changed unexpected.
Therefore AR Output (AR.OUT.Value) is uncertainty. (AL-92)
[Remedy]: Set the AR Compensation Coeffi cient (AR.AR_FLOW_CONFIG.element)
again.

RS DEVICE_
STATUS_5 bit6

AR Output Unit
Conf. Err (AL-93)

AL-93

AR Output Range. Units Index (AR.OUT_RANGE.Unit Index) is not selected rightly the
corresponding to AR Arithmetic Type (AR.ARITH_TYPE) (AL-93).
[Remedy]: Refer to IM or Check the AR Output Range. Units Index (AR.OUT_RANGE.
Unit Index) and AR Arithmetic Type (AR.ARITH_TYPE).

RS DEVICE_
STATUS_5 bit5

Table A12.6 Additional Information

Alarm item

Alarm No.

Description

Parameter

Output of AI1

The primary value calculated as a result of executing the function in AI1

AI01. OUT

Total

Indicates the totalized value

AI01. TOTAL

Output of AI2

The primary value calculated as a result of executing the function in AI2

AI02. OUT

Output of DI1

The primary value calculated as a result of executing the function in DI1

DI01. OUT_D

Output of DI2

The primary value calculated as a result of executing the function in DI2

DI02. OUT_D