A3-3 – Yokogawa digitalYEWFLO (DY-FF) User Manual

Page 83

Advertising
background image

<APPENDIX 3. OPERATION OF EACH PARAMETER IN FAILURE MODE>

A3-3

IM 01F06F00-01EN

LCD

Display

Alarm Detail

DI1 Block

DI2 Block

PID Block

IT Block

AR Block

Alarm Reset SW*

(default)

AL-01

AMP. Module
Failure 1 (AL-01)

<PV_D.Status>
• Default
Bad-Non Specifi c
• STATUS_OPTS:
Propagate Fault Forward=Active
Bad-Device Failure

Not provided

<OUT_D.Status>
• Default
Bad-Non Specifi c
• STATUS_OPTS:
Propagate Fault Forward=Active
Bad-Device Failure

AL-02

COM. Circuit
Failure 1 (AL-02)

<PV_D.Status>
• Default
Bad-Non Specifi c
• STATUS_OPTS:
Propagate Fault Forward=Active
Bad-Device Failure

Not provided

<OUT_D.Status>
• Default
Bad-Non Specifi c
• STATUS_OPTS:
Propagate Fault Forward=Active
Bad-Device Failure

AL-03

COM. Circuit
Failure 2 (AL-03)

<PV_D.Status>
• Default
Bad-Non Specifi c
• STATUS_OPTS:
Propagate Fault Forward=Active
Bad-Device Failure

Not provided

<OUT_D.Status>
• Default
Bad-Non Specifi c
• STATUS_OPTS:
Propagate Fault Forward=Active
Bad-Device Failure

AL-04

AMP. Module
Failure 2 (AL-04)

<PV_D.Status>
Bad-Non Specifi c

Not provided

<OUT_D.Status>
Bad-Non Specifi c

AL-05

Flow Sensor
Failure (AL-05)

<PV_D.Status>
• TARGET in TB’s LIMSW =
PRIMARY_VALUE Uncertain-Non Specifi c

Provided

(ON)

<OUT_D.Status>
• TARGET in TB’s LIMSW =
PRIMARY_VALUE Uncertain-Non Specifi c