<APPENDIX 7. LINK MASTER FUNCTIONS>

A7-9

IM 01F06F00-01EN

A4-2. Make the parameters in the current LAS

match the capabilities parameter in the
digitalYEWFLO as follows (Refer to Section
5.2 “Network Defi nition”):

LAS

digitalYEWFLO

V(ST)

>

V(ST)

≥ 4

V(MID)

>

V(MID)

≥ 4

V(MRD)

>

V(MRD)

≥ 12

A4-3. Check that the digitalYEWFLO is assigned

an appropriate address. The address of
the digitalYEWFLO must not lie within
either 0x00 to 0x10 or the range of unused
(unpolled) node addresses determined by
the current LAS’s LM parameter settings,
which is V(FUN) to V(FUN) + V(NUM).
(Refer to Section 5.2 “Network Defi nition.”)