<APPENDIX 3. OPERATION OF EACH PARAMETER IN FAILURE MODE>

A3-15

IM 01F06F00-01EN

Alarm Reset Switch Settings
Some alarms can be disabled and enabled using switches in parameter ALARM_PERFORM inside the

transducer block as explained below.

(1) Setting

As shown in the following table, the individual bits of ALARM_PERFORM at relative index 45 act as

switches to disable and enable particular alarms. Write zeros to the respective bits to disable desired
alarms, or write ones to enable them.

(2) Default Values

Bit in

ALARM_PERFORM

Corresponding Alarms

Factory Default

(0 = Disable; 1 = Enable)

Bit 15

AL-84 to AL-93 (alarms pertaining to AR)

0

Bit 14

AL-80 to AL-83 (alarms pertaining to IT)

0

Bit 13

AL-77 to AL-79 (alarms pertaining to AI3)

0

Bit 12

AL-62 to AL-64 (alarms pertaining to AI1)

1

Bit 11

AL-65 to AL-67 (alarms pertaining to AI2)

0

Bit 10

AL-68 to AL-70 (alarms pertaining to DI1)

0

Bit 9

AL-71 to AL-73 (alarms pertaining to DI2)

0

Bit 8

AL-74 to AL-76 (alarms pertaining to PID)

0

Bit 7

Not used.

Bit 6

Corresponds to parameter K45 in a non-Fieldbus type digitalYEWFLO.
Selects the output action upon occurrence of “High Vibration” in self-diagnostics.

1

Bit 5

AL-05 (fl ow sensor fault)

1

Bit 4

AL-06 (failure of amplifi er’s input circuit)

1

Bit 3

AL-51 (transient excessive vibration [transient disturbance])

0

Bit 2

AL-52 (excessive vibration)

0

Bit 1

AL-53 (fl ow anomaly [clogging])

0

Bit 0

AL-54 (fl ow anomaly [excessive output fl uctuations])

0

These default bit statuses comprise 0x1070 as the default value of ALARM_PERFORM.