<APPENDIX 6. Enhanced ARITHMETIC (AR) BLOCK>

A6-8

IM 01F06F00-01EN

Relative

Index

Parameter

Write Mode

Initial
Value

Description / Remarks

29 ARITH_TYPE

AUTO

0x01

Computation algorithm identifi cation no.

Value

Selection Name

Description

1

Flow compensation, linear

Flow compensation (linear)

2

Flow compensation, square root Flow compensation (square root)

3

Flow compensation, approximate Flow compensation (approximate expression)

4

BTU fl ow (*)

Quantity of heat calculation

5

Traditional Multiply Divide

Multiplication and division

6

Average

Average calculation

7

Traditional summer

Summation

8

Fourth order Polynomial, (Type 1) 4th-order (auxiliary input) polynomial computation

9

HTG level compensation (*)

HTG-level compensation

10

Fourth order Polynomial, (Type 2) 4th-order (main input) polynomial computation

11 to 31 Reserve

For reserve of FF Std calculation.

32

Saturated steam (Temperature)

Density calculation of Sat.Steam (Temp.)

33

Saturated steam (Pressure)

Density calculation of Sat.Steam (Press.)

34

Superheat steam

Gas Temp./Press. compensation calculation
(Deviation factor: Fixed).

35

Gas temperature pressure
compensation

Density calculation of S.H.Steam

36

Liquid temperature compensation Liquid Temp. compensation Calculation

37

Gas temperature pressure
compensation (Detail)

Gas Temp./Press. compensation calculation
(approximating polynomial calculation: 0 to 11).

38

Liquid temperature compensation
(Detail)

Liquid Temp./Press. compensation calculation
(approximating polynomial calculation: 0 to 3).

* BTU stands for British thermal unit.

HTG stands for hydrostatic tank gauging.

30

BAL_TIME

AUTO

0

Time taken to return to the set value

31

BIAS

AUTO

0

Bias value used to calculate the output

32

GAIN

AUTO

1

Gain value used to calculate the output

33

OUT_HI_LIM

AUTO

+INF Maximum output value

34

OUT_LO_LIM

AUTO

-INF Minimum output value

35

UPDATE_EVT

Indicates event information if an update event (setting change) occurs.

36

BLOCK_ALM

Indicates alarm information if a block alarm occurs.

37

AR_
VOLUMETRIC_
FLOW_UNIT

O/S

m

3

/h

(1349)

Volumetric fl ow unit

38

AR_
TEMPERATURE_
UNIT

O/S

°C

(1001)

Temperature unit

39

AR_BASE_
TEMPERATURE

MAN

0.0

Temperature unit at normal condition

40

AR_
PRESSURE_
UNIT

O/S

MPa

(1132)

Pressure unit

41

AR_BASE_
PRESSURE_ABS

MAN

0.1013 Pressure unit at normal condition (abs)

42 AR_DEVIATION

MAN

1.0

Deviation

factor

43

AR_DENSITY_
UNIT

O/S

kg/m

3

(1097)

Density unit

44

AR_BASE_
DENSITY

MAN

1.0

Density unit at normal condition

45

AR_FIRST_
TEMP_COEF

MAN 0.0

1

st

temperature coeffi cient for liquid

46

AR_SECOND_
TEMP_COEF

MAN 0.0

2

nd

temperature coeffi cient for liquid

47

AR_FLOW_
CONFIG

MAN

all

0.0

A polynomial coeffi cient for density calculation (16)
Gas Temp./Press. Calculation (Detail): use FLOW_CONFIG[0] to [11]
Liquid calculation (Detail): use FLOW_CONFIG [0] to [3]

48

AR_DENSITY_
FACTOR

— —

Correction value:
Mass fl ow output: density at operating condition
Volumetric fl ow output: ratio of density at operation condition to density at normal
condition.)

49

AR_DENSITY_
FACTOR_UNIT

Correction value unit. (The unit is indicated only for density at operation condition.)