A5.2 Input Process Section

When executed, the Integrator block fi rst performs
input processing in the order of:
“Determining input status”

 “Converting Rate or

Accum”

 “Determining the input fl ow direction”

Switching between Convert Rate and Convert
Accum is made using bit 0 (for IN_1) or bit 1 (for
IN_2) of INTEG_OPTS. INTEG_OPTS is one of the
system parameters and should be set by the user.
The values of IN_1 and IN_2 are not retained if the
power is turned OFF.

A5.2.1 Determining Input Value Statuses

The following shows the correlation between the statuses of input parameters (IN_1, IN_2) and the statuses of
input values used in the Integrator block.

Statuses of Input

Parameters (IN_1, IN_2)

Bit 4 of INTEG_OPTS

(Use Uncertain)

Bit 5* of INTEG_OPTS

(Use Bad)

Status of Input Values

Handled in IT Block

Good

Irrelevant

Irrelevant

Good

Bad

Irrelevant

H (=1)

Good

Bad

Irrelevant

L (=0)

Bad

Uncertain

H (=1)

Irrelevant

Good

Uncertain

L (=0)

Irrelevant

Bad

For addition (Refer to APPENDIX 5.3 “Adder”), if the status of an input value is “Bad,” the “Good” value just
before the status changed to “Bad” is used.

* Even if the Use Bad option is used, changing the internal status to “Good,” the value of “Good” just before the

status changed to “Bad” is used.

A5.2.2 Converting the Rate

The following describes an example of rate
conversion.
In rate conversion, fi rstly convert the unit of two
inputs to that based on seconds.

Next, convert the unit of the inputs to the same
unit to be added together. The unit of IN_2 is
standardized to that of IN_1. Then, calculates a
weight, volume, or energy by multiplying each
input value and block execution time. Because unit
information is not input to the Integrator block as an
input value, the user must input in advance tuned
values to the TIME_UNIT1/2 and UNIT_CONV
parameters.

TIME_UNIT1

sec:÷1

min:÷60

hour:÷3600

day:÷86400

input1

kg/hour

input2

lb/s

kg/s

kg

increment2

increment1

lb/min

lb: pounds

Converts the unit into

that based on seconds

Standardizes the unit of
IN_2 to that of IN_1.
Because “lb/s” is converted into
“kg/s” in this example, the input
2 value is multiplied by 0.453.
(1 lb = 0.453 kg)

UNIT_CONV

x [conversion factor]

(Conversion factor:

0.453 in this example)

Converts the unit into

that based on seconds

TIME_UNIT2

sec:÷1

min:÷60

hour:÷3600

day:÷86400

kg/s

kg

u block execution time

u block execution time

FA0502.ai

Figure A5.2 Increment Calculation with Rate Input

<APPENDIX 5. INTEGRATOR (IT) BLOCK>

A5-2

IM 01F06F00-01EN