<APPENDIX 8. PID BLOCK>

A8-3

IM 01F06F00-01EN

Index Parameter Name

Default

(factory setting)

Write Valid

Range

Description

36 ROUT_OUT

0

Remote control output value

37 TRK_SCALE

100

0

1342 (%)

1

MAN

Upper and lower scale limits used to convert the output
tracking value (TRK_VAL) to non-dimensional.

38 TRK_IN_D

0

Switch for output tracking. Refer to APPENDIX 8.12
“External-output Tracking” for details.

39 TRK_VAL

0

Output tracking value (TRK_VAL)
When MODE_BLK.actual = LO, the value scaled from the
TRK_VAL value is set in OUT.

40 FF_VAL

0

Feedforward input value.
The FF_VAL value is scaled to a value with the same scale
as for OUT, multiplied by the FF_GAIN value, and then
added to the output of the PID computation.

41 FF_SCALE

100

0

1342 (%)

1

MAN

Scale limits used for converting the FF_VAL value to a non-
dimensional value.

42 FF_GAIN

0

MAN

Gain for FF_VAL

43 UPDATE_EVT

Same as that for an AI block.

44 BLOCK_ALM

Same as that for an AI block.

45 ALARM_SUM

Enable

Same as that for an AI block.

46 ACK_OPTION

0

Same as that for an AI block.

47 ALARM_HYS

0.5%

0 to 50%

Hysteresis for alarm detection and resetting to prevent each
alarm from occurring and recovering repeatedly within a
short time.

48 HI_HI_PRI

0

0 to 15

Priority order of HI_HI_ALM alarm

49 HI_HI_LIM

1.#INF

PV_SCALE

Setting for HI_HI_ALM alarm

50 HI_PRI

0

0 to 15

Priority order of HI_ALM alarm

51 HI_LIM

1.#INF

PV_SCALE

Setting for HI_ALM alarm

52 LO_PRI

0

0 to 15

Priority order of LO_ALM alarm

53 LO_LIM

-1.#INF

PV_SCALE

Setting for LO_ALM alarm

54 LO_LO_PRI

0

0 to 15

Priority order of LO_LO_ALM alarm

55 LO_LO_LIM

-1.#INF

PV_SCALE

Setting for LO_LO_ALM alarm

56 DV_HI_PRI

0

0 to 15

Priority order of DV_HI_ALM alarm

57 DV_HI_LIM

1.#INF

Setting for DV_HI_ALM alarm

58 DV_LO_PRI

0

0 to 15

Priority order of DV_LO_ALM alarm

59 DV_LO_LIM

-1.#INF

Setting for DV_LO_ALM alarm

60 HI_HI_ALM

Alarm that is generated when the PV value has exceeded
the HI_HI_LIM value and whose priority order* is defi ned in
HI_HI_PRI.
* Priority order: Only one alarm is generated at a time.
When two or more alarms occur at the same time, the alarm
having the highest priority order is generated. When the
PV value has decreased below [HI_HI_LIM – ALM_HYS],
HI_HI_ALM is reset.

61 HI_ALM

As

above

62 LO_ALM

As

above

Reset when the PV value has increased above
[LO_LIM + ALM_HYS].

63 LO_LO_ALM

As

above

64 DV_HI_ALM

Alarm that is generated when the value of [PV - SP] has
exceeded the DV_HI_LIM value. Other features are the
same as HI_HI_ALM.

65 DV_LO_ALM

Alarm that is generated when the value of [PV - SP] has
decreased below the DV_LO_LIM value. Other features are
the same as LO_LO_ALM.