Table A12.1 Hardware Failure

Alarm item

Alarm No.

Description

Parameter

AMP. Module
Failure 1 (AL-01)

AL-01

The EEPROM(S) failed. (AL-01)
[Remedy]: Contact the nearest offi ce or service center.

RS DEVICE_
STATUS_2 bit0

COM. Circuit
Failure 1 (AL-02)

AL-02

The serial communication circuit in the amplifi er failed (type 1 error). (AL-02)
[Remedy]: Contact the nearest offi ce or service center.

RS DEVICE_
STATUS_2 bit1

COM. Circuit
Failure 2 (AL-03)

AL-03

The serial communication circuit in the amplifi er failed (type 2 error). (AL-03)
[Remedy]: Contact the nearest offi ce or service center.

RS DEVICE_
STATUS_2 bit2

AMP. Module
Failure 2 (AL-04)

AL-04

The EEPROM(F) failed. (AL-04)
[Remedy]: Contact the nearest offi ce or service center.

RS DEVICE_
STATUS_1 bit19

Flow Sensor
Failure (AL-05)

AL-05

The fl ow sensor failed. (AL-05)
[Remedy]: Contact the nearest offi ce or service center.

RS DEVICE_
STATUS_2 bit3

Input Circuit
Failure (AL-06)

AL-06

The input circuit in the amplifi er failed. (AL-06)
[Remedy]: Contact the nearest offi ce or service center.

RS DEVICE_
STATUS_2 bit4

Temp. Converter
Failure (AL-07)

AL-07

The temperature circuit in the amplifi er failed. (AL-07)
[Remedy]: Contact the nearest offi ce or service center.

RS DEVICE_
STATUS_2 bit5

Temp. Sensor
Failure (AL-08)

AL-08

The temperature sensor failed. (AL-08)
[Remedy]: Contact the nearest offi ce or service center.

RS DEVICE_
STATUS_2 bit6

Table A12.2 Transducer Status

Alarm item

Alarm No.

Description

Parameter

Flow Rate Over
Range (AL-41)

AL-41

Flow rate is over the range. (AL-41)
[Remedy]: This case is out of specifi cations. Check the process fl ow.

RS DEVICE_
STATUS_4 bit7

Flow Span
Exceed Limit
(AL-42)

AL-42

The fl ow rate span setting exceeds the range limit. (AL-42)
[Remedy]: Check the TB and AI1 parameters.

RS DEVICE_
STATUS_4 bit6

Temp. Over
Range (AL-43)

AL-43

Temperature is over the range. (AL-43)
(Regulated in the upper or lower limit value)
[Remedy]: This case is out of specifi cations. Check the process temperature.

RS DEVICE_
STATUS_4 bit5

Transient
Vibration (AL-51)

AL-51

The transient vibration makes the current fl ow rate output constant. (AL-51)
[Remedy]: Check the pipeline condition. When this alarm occurs several time, contact the
nearest offi ce or service center.

RS DEVICE_
STATUS_4 bit3

High Vibration
(AL-52)

AL-52

The high vibration makes the current fl ow rate output zero. (AL-52)
[Remedy]: In case of outputting the current fl ow rate, Change the value of High vibration
output select in TB Alarm Perform(TB.ALARM_PERFORM) to ON. When this alarm
occurs several time, contact the nearest offi ce or service center.

RS DEVICE_
STATUS_4 bit2

Clogging (AL-53)

AL-53

The shedder bar is clogged with a material. (AL-53)
[Remedy]: Remove a material according to device manual (IM 01F06F00-01EN).

RS DEVICE_
STATUS_4 bit1

Fluctuating
(AL-54)

AL-54

The current fl ow rate is fl uctuating more than 20%. (AL-54)
[Remedy]: Check the pipeline condition. When this alarm occurs several time, contact the
nearest offi ce or service center.

RS DEVICE_
STATUS_4 bit0

Indicator Over
Range (AL-61)

AL-61

Indicator is over the range. (AL-61)
[Remedy]: Check the value of AI1 Transducer Scale (AI1.XD_SCALE) or AI1 Output
Scale (AI1.OUT_SCALE).

RS DEVICE_
STATUS_4 bit0

SoftDL
Incomplete

-

Software download is incomplete.
[Remedy]: Check the cables, power, and RB Softdown Error (RB.SOFTDOWN_
ERROR).

RS DEVICE_
STATUS_1 bit24

SoftDL Failure

-

Software download failed.
[Remedy]: Check the download fi le and RB Softdown Error (RB.SOFTDOWN_ERROR).

RS DEVICE_
STATUS_1 bit25

Abnormal Boot
Process

-

Abnormal boot processing was detected at the time of startig.
[Remedy]: Check cable, power and RB.SOFTDWN_ERROR (RB.SOFTDOWN_
ERROR).

RS DEVICE_
STATUS_1 bit26