<APPENDIX 6. Enhanced ARITHMETIC (AR) BLOCK>

A6-3

IM 01F06F00-01EN

A6.2.3 INPUT_OPTS

INPUT_OPTS has an option that handles an input
with “uncertain” or “bad” status as a “good” status
input.

Bit

Function

0

Handles IN as a “good” status input if its status is
“uncertain.”

1

Handles IN_LO as a “good” status input if its status is
“uncertain.”

2

Handles IN_1 as a “good” status input if its status is
“uncertain.”

3

Handles IN_1 as a “good” status input if its status is
“bad.”

4

Handles IN_2 as a “good” status input if its status is
“uncertain.”

5

Handles IN_2 as a “good” status input if its status is
“bad.”

6

Handles IN_3 as a “good” status input if its status is
“uncertain.”

7

Handles IN_3 as a “good” status input if its status is
“bad.”

8 to 15 Reserved

There are options called “IN Use uncertain” and
“IN_LO Use uncertain” for the IN and IN_LO inputs.
When these options are valid, IN and IN_LO are
internally interpreted as “good” IN and IN_LO even
if their statuses are “uncertain.” (There is no option
for “bad” status.)
For the IN_1, IN_2, and IN_3 auxiliary inputs, there
are options known as “IN_i Use uncertain” and “IN_i
Use bad.” If these options are valid, an IN_i with
“uncertain” or “bad” status is internally interpreted
as a “good” IN_i.
* The exception is that if the input status is “Bad.

Not Connected,” INPUT_OPTS does not apply
and the input is considered “bad” as is.

A6.2.4 Relationship between the Main

Inputs and PV

The value and PV status are determined by the
statuses of two main inputs, INPUT_OPTS, and
RANGE_LO and RANGE_HI.
· If the statuses of two main inputs are both “good”

or anything other than “good”, refer to APPENDIX
6.2.1 “Main Inputs.”

· If only one of two main inputs has “good” status

after application of INPUT_OPTS, the PV value is
determined as follows:
• If the status of IN is “good” and that of “IN_LO”

is anything other than “good”

IN > RANGE_LO

 PV = IN

IN

≤ RANGE_LO  Refer to APPENDIX

6.2.1 “Main Inputs.”

• If the status of IN is anything other than “good”

and that of “IN_LO” is “good”

IN_LO < RANGE_HI

 PV = IN_LO

IN_LO

≥ RANGE_H  Refer to APPENDIX

6.2.1 “Main Inputs.”

RANGE_LO

RANGE_HI

PV = IN_LO

PV = IN

PV = g

× IN + (1-g) × IN_LO

PV = g

× IN + (1-g) × IN_LO

IN

IN_LO

FA0603.ai

If the status of IN is “good” and that of “IN_LO” is
anything other than “good”

If the status of IN is anything other than “good”
and that of “IN_LO” is “good”